c. On all units, remove blower assembly from unit. Re-

move screws securing blower to blower partition and
slide assembly out. Be careful not to tear insulation in
blower compartment.

d. Ensure proper reassembly by marking blower wheel and

motor in relation to blower housing before disassembly.

e. Loosen setscrew(s) that secures wheel to motor shaft,

remove screws that secure motor mount brackets to
housing, and slide motor and motor mount out of
housing.

2. Remove and clean blower wheel as follows:

a. Ensure proper reassembly by marking wheel orientation.

b. Lift wheel from housing. When handling and/or cleaning

blower wheel, be sure not to disturb balance weights
(clips) on blower wheel vanes.

c. Remove caked-on dirt from wheel and housing with a

brush. Remove lint and/or dirt accumulations from wheel
and housing with vacuum cleaner, using soft brush
attachment. Remove grease and oil with mild solvent.

d. Reassemble wheel into housing.

e. Reassemble motor into housing. Be sure setscrew(s) are

tightened on motor shaft flats and not on round part of
shaft.

f. Reinstall unit access panel.

3. Restore electrical power, then gas supply to unit. Start unit

and check for proper blower rotation and motor speeds
during heating and cooling cycles.

C.

Flue Gas Passageways

To inspect the flue collector box and upper areas of the heat
exchanger:

TABLE 9—WET COIL AIR DELIVERY* — HORIZONTAL AND DOWNFLOW DISCHARGE

UNIT 583B030-060

(DEDUCT 10% FOR 208 VOLTS)

230 AND 460 VOLT

Unit

583B

Motor

Speed

External Static Pressure (in. wg)

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

030

Low

Watts

243

244

242

Cfm

885

842

786

Medium

Watts

353

339

333

330

326

320

Cfm

1195

1134

1070

997

911

818

High

Watts

443

436

426

416

406

397

Cfm

1230

1145

1061

977

888

786

036

Low

Watts

490

463

446

432

418

403

389

378

Cfm

1431

1398

1347

1281

1205

1118

1024

921

Medium

Watts

513

501

488

474

459

443

428

Cfm

1491

1426

1351

1267

1175

1077

976

High

Watts

645

636

627

616

605

593

583

Cfm

1484

1410

1330

1243

1147

1044

936

042

Low

Watts

634

618

608

598

583

562

534

502

473

454

457

Cfm

1669

1599

1545

1498

1448

1391

1326

1257

1189

1132

1101

Medium

Watts

733

704

672

638

604

574

550

536

Cfm

1746

1688

1630

1566

1492

1399

1279

1120

High

Watts

797

773

751

727

696

Cfm

1727

1632

1537

1423

1308

048

Low

Watts

591

578

573

568

559

544

524

500

Cfm

1554

1523

1496

1467

1432

1387

1332

1269

Medium

Watts

755

737

719

699

678

653

627

602

579

562

556

Cfm

1834

1802

1758

1706

1648

1585

1520

1455

1392

1332

1276

High

Watts

890

858

828

801

777

756

734

709

Cfm

1943

1870

1793

1711

1624

1531

1433

1329

060

Low

Watts

589

576

569

566

559

541

499

Cfm

1946

1891

1836

1779

1718

1651

1577

Medium

Watts

750

733

715

695

673

648

623

598

577

Cfm

2189

2097

2021

1952

1883

1809

1727

1635

1530

High

Watts

879

850

821

795

772

750

728

701

Cfm

2337

2159

2050

1974

1905

1824

1722

1597

*Air delivery values are without air filter.
Note: Deduct field-supplied air filter pressure drop to obtain external static pressure available for ducting.