c. On all units, remove blower assembly from unit. Re-
move screws securing blower to blower partition and
slide assembly out. Be careful not to tear insulation in
blower compartment.
d. Ensure proper reassembly by marking blower wheel and
motor in relation to blower housing before disassembly.
e. Loosen setscrew(s) that secures wheel to motor shaft,
remove screws that secure motor mount brackets to
housing, and slide motor and motor mount out of
housing.
2. Remove and clean blower wheel as follows:
a. Ensure proper reassembly by marking wheel orientation.
b. Lift wheel from housing. When handling and/or cleaning
blower wheel, be sure not to disturb balance weights
(clips) on blower wheel vanes.
c. Remove caked-on dirt from wheel and housing with a
brush. Remove lint and/or dirt accumulations from wheel
and housing with vacuum cleaner, using soft brush
attachment. Remove grease and oil with mild solvent.
d. Reassemble wheel into housing.
e. Reassemble motor into housing. Be sure setscrew(s) are
tightened on motor shaft flats and not on round part of
shaft.
f. Reinstall unit access panel.
3. Restore electrical power, then gas supply to unit. Start unit
and check for proper blower rotation and motor speeds
during heating and cooling cycles.
C.
Flue Gas Passageways
To inspect the flue collector box and upper areas of the heat
exchanger:
TABLE 9—WET COIL AIR DELIVERY* — HORIZONTAL AND DOWNFLOW DISCHARGE
UNIT 583B030-060
(DEDUCT 10% FOR 208 VOLTS)
230 AND 460 VOLT
Unit
583B
Motor
Speed
External Static Pressure (in. wg)
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
030
Low
Watts
243
244
242
–
–
–
–
–
–
–
–
Cfm
885
842
786
–
–
–
–
–
–
–
–
Medium
Watts
353
339
333
330
326
320
–
–
–
–
–
Cfm
1195
1134
1070
997
911
818
–
–
–
–
–
High
Watts
–
–
–
443
436
426
416
406
397
–
–
Cfm
–
–
–
1230
1145
1061
977
888
786
–
–
036
Low
Watts
490
463
446
432
418
403
389
378
–
–
–
Cfm
1431
1398
1347
1281
1205
1118
1024
921
–
–
–
Medium
Watts
–
513
501
488
474
459
443
428
–
–
–
Cfm
–
1491
1426
1351
1267
1175
1077
976
–
–
–
High
Watts
–
–
645
636
627
616
605
593
583
–
–
Cfm
–
–
1484
1410
1330
1243
1147
1044
936
–
–
042
Low
Watts
634
618
608
598
583
562
534
502
473
454
457
Cfm
1669
1599
1545
1498
1448
1391
1326
1257
1189
1132
1101
Medium
Watts
–
–
–
733
704
672
638
604
574
550
536
Cfm
–
–
–
1746
1688
1630
1566
1492
1399
1279
1120
High
Watts
–
–
–
–
–
–
797
773
751
727
696
Cfm
–
–
–
–
–
–
1727
1632
1537
1423
1308
048
Low
Watts
591
578
573
568
559
544
524
500
–
–
–
Cfm
1554
1523
1496
1467
1432
1387
1332
1269
–
–
–
Medium
Watts
755
737
719
699
678
653
627
602
579
562
556
Cfm
1834
1802
1758
1706
1648
1585
1520
1455
1392
1332
1276
High
Watts
–
–
–
890
858
828
801
777
756
734
709
Cfm
–
–
–
1943
1870
1793
1711
1624
1531
1433
1329
060
Low
Watts
589
576
569
566
559
541
499
–
–
–
–
Cfm
1946
1891
1836
1779
1718
1651
1577
–
–
–
–
Medium
Watts
750
733
715
695
673
648
623
598
577
–
–
Cfm
2189
2097
2021
1952
1883
1809
1727
1635
1530
–
–
High
Watts
–
879
850
821
795
772
750
728
701
–
–
Cfm
–
2337
2159
2050
1974
1905
1824
1722
1597
–
–
*Air delivery values are without air filter.
Note: Deduct field-supplied air filter pressure drop to obtain external static pressure available for ducting.
Fig. 25—Blower Housing and Flue Collector Box
C99022
INDUCED DRAFT MOTOR MOUNT
FLUE
COLLECTOR
BOX
BLOWER
HOUSING
BURNER
RACK
MOUNTING
SCREW
ROLLOUT
SWITCH
—21—