TABLE 11—TROUBLESHOOTING — HEATING

SYMPTOM

CAUSE

REMEDY

Burners will not ignite.

Water in gas line

Drain. Install drip leg.

No power to furnace

Check power supply fuses, wiring, or circuit breaker.

Miswired or loose connections

Check all wiring and wirenut connections.

Burned-out heat anticipator in thermostat

Replace thermostat.

Broken thermostat wire

Run continuity check. Replace wire if necessary.

Misaligned spark electrodes

Check flame ignition and sense electrode positioning.

Adjust as necessary

No gas at main burners

1. Check gas line for air. Purge as necessary. NOTE:

After purging gas line of air, wait at least 5 minutes for

any gas to dissipate before attempting to light unit.

2. Check gas valve.

Inadequate heating.

Dirty air filter

Clean or replace filter as necessary.

Gas input to furnace too low

check gas pressure at manifold. Match with that on unit

nameplate.

Unit undersized for application

Replace with proper unit or add additional unit.

Restricted airflow

Clean or replace filter. Remove any restriction.

Blower speed too low

Use faster speed tap if available, or install alternate

motor.

Limit switch cycles main burners

Check rotation of blower, thermostat heat anticipator

settings, and temperature rise of unit. Adjust as neces-

sary.

Poor flame. characteristics

Incomplete combustion results in: Aldehyde odors, car-

bon monoxide, sooting flame, floating flame

1. Tighten all screws around burner compartments.

2. Cracked heat exchanger. Replace

3. Unit overfired. Reduce input (change orifices or ad-

just gas line or manifold pressure).

4. Check burner alignment.