Bryant R-410A 583B User Manual

Page 12

background image

TABLE 5—ELECTRICAL DATA — 583B

UNIT

SIZE 583B

V-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

OUTDOOR FAN MOTOR

INDOOR FAN MOTOR

POWER SUPPLY

Min

Max

RLA

LRA

FLA

FLA

MCA

MOCP*

030

208/230-3-60

187

253

9.6

63.0

0.8

2.1

14.9

20

036

208/230-3-60

187

253

12.2

77.0

0.8

3.6

19.7

30

460-3-60

414

506

5.1

35.0

0.8

1.9

9.1

15

042

208/230-3-60

187

253

13.5

77.0

1.6

4.1

22.6

35

460-3-60

414

506

6.3

39.0

0.9

2.0

10.8

15

048

208/230-3-60

187

253

14.7

91.0

1.6

4.1

24.1

35

460-3-60

414

506

6.5

46.0

0.9

2.0

11.0

15

060

208/230-3-60

187

253

18.1

137.0

1.6

6.2

30.4

45

460-3-60

414

506

9.0

62.0

0.9

3.2

15.4

20

452 = 5 v

457 = 7 v
455 = 2 v

LEGEND

FLA

— Full Load Amps

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
RLA

— Rated Load Amps

NOTES:
1. In compliance with NEC (National Electrical Code) requirements

for multimotor and combination load equipment (refer to NEC
Articles 430 and 440), the overcurrent protective device for the
unit shall be Power Supply fuse . Canadian units may be
fuse or circuit breaker.

2. Minimum wire size is based on 60 C copper wire. If other than

60 C wire is used, or if length exceeds wire length in table,
determine size from NEC.

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-
age is greater than 2%. Use the following formula to determine
the percentage of voltage imbalance.

% Voltage imbalance

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457
(BC) 464
(AC) 457

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is
more than 2%, contact your local electric utility company
immediately.

®

CKT BKR — Circuit Breaker

C99024

Fig. 13—Electrical Data Legend

Fig. 14—High- and Control-Voltage Connections

C99018

POWER
SUPPLY

FIELD-SUPPLIED
FUSED DISCONNECT

HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)

GND

CONTROL BOX

SPLICE BOX

LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL)

W

Y

G

R

C

WHT(W1)

YEL(Y)

GRN(G)

RED(R)

BRN(C)

THERMOSTAT
(TYPICAL)

—12—