Fig. 7—583B042-060 Unit Dimensions

C99074

UNIT

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

UNIT HEIGHT

IN. (MM)

"A"

CENTER OF GRAVITY

IN. (MM)

lb.

kg.

X

Y

Z

583B042060/090

208/230-3-60

460-3-60

382

173.3

38.98 (990.2)

23.0 (584.2)

16.3 (412.8)

16.6 (421.6)

583B048090/115/130

208/230-3-60

460-3-60

421

191.0

38.98 (990.2)

21.5 (546.1)

16.6 (422.1)

18.0 (457.2)

583B060090/115/130

208/230-3-60,

460-3-60

468

212.3

42.98 (1091.7)

23.5 (596.9)

16.3 (412.8)

17.6 (447.0)

REQUIRED CLEARANCE FOR OPERATION AND SERVICING

in. [mm]

EVAP. COIL ACCESS SIDE..............................................................36.00 [914.0]
POWER ENTRY SIDE......................................................................36.00 [914.0]
(EXCEPT FOR NEC REQUIREMENTS)
UNIT TOP .........................................................................................36.00 [914.0]
SIDE OPPOSITE DUCTS ................................................................36.00 [914.0]
DUCT PANEL ...................................................................................12.00 [304.8] *

*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 12.00 [304.8] FROM
WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.

in. [mm]

TOP OF UNIT...................................................................................14.00 [355.6]
DUCT SIDE OF UNIT.........................................................................2.00 [50.8]
SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]
BOTTOM OF UNIT .............................................................................0.50 [12.7]

FLUE HEAT PANEL

.................................................................36.00 [914.4]

NEC. REQUIRED CLEARANCES.

in. [mm.]

BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]
UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE ...36.00 [914.0]
UNIT AND BLOCK OR CONCRETE WALLS AND OTHER
GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]

FLUE HOOD

—6—