Bryant R-410A 583B User Manual
Page 26
TABLE 10—TROUBLESHOOTING — COOLING
SYMPTOM
CAUSE
REMEDY
Compressor and condenser fan will not start.
Power failure
Call power company.
Fuse blown or circuit breaker tripped
Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer,
control relay, high pressure, or loss of charge
switch
Replace component.
Insufficient line voltage
Determine cause and correct.
Incorrect or faulty wiring
Check wiring diagram and rewire correctly.
Thermostat setting too high
Lower thermostat setting below room tempera-
ture.
Compressor will not start but condenser fan
runs.
Faulty wiring or loose connections in compres-
sor circuit
Check wiring and repair or replace.
Compressor motor burned out, seized, or inter-
nal overload open
Determine cause. Replace compressor.
Defective run/start capacitor, overload, start re-
lay
Determine cause and replace.
One leg of 3-phase power dead
Replace fuse or reset circuit breaker. Determine
cause.
Three-phase scroll compressor makes ex-
cessive noise, and there may be a low pres-
sure differential.
Scroll compressor is rotating in the wrong direc-
tion
Correct the direction of rotation by reversing the
3-phase power leads to the unit. Shut down unit
to allow pressures to equalize.
Compressor cycles (other than normally sat-
isfying thermostat).
Refrigerant overcharge or undercharge
Recover refrigerant, evacuate system, and re-
charge to capacities shown on nameplate.
Defective compressor
Replace and determine cause.
Insufficient line voltage
Determine cause and correct.
Blocked condenser
Determine cause and correct.
Defective run/start capacitor, overload or start
relay
Determine cause and replace.
Defective thermostat
Replace thermostat.
Faulty condenser-fan motor or capacitor
Replace.
Restriction in refrigerant system
Locate restriction and remove.
Compressor operates continuously.
Dirty air filter
Replace filter.
Unit undersized for load
Decrease load or increase unit size.
Thermostat set too low
Reset thermostat.
Low refrigerant charge
Locate leak, repair, and recharge.
Leaking valves in compressor
Replace compressor.
Air in system
Recover refrigerant, evacuate system, and re-
charge.
Condenser coil dirty or restricted
Clean coil or remove restriction.
Excessive head pressure.
Dirty air filter
Replace filter.
Dirty condenser coil
Clean coil.
Refrigerant overcharged
Recover excess refrigerant.
Air in system
Recover refrigerant, evacuate system, and re-
charge.
Condenser air restricted or air short-cycling
Determine cause and correct.
Head pressure too low.
Low refrigerant charge
Check for leaks, repair and recharge.
Compressor valves leaking
Replace compressor.
Restriction in liquid tube
Remove restriction.
Excessive suction pressure.
High heat load
Check for source and eliminate.
Compressor valves leaking
Replace compressor.
Refrigerant overcharged
Recover excess refrigerant.
Suction pressure too low.
Dirty air filter
Replace filter.
Low refrigerant charge
Check for leaks, repair and recharge.
Metering device or low side restricted
Remove source of restriction.
Insufficient evaporator airflow
Increase air quantity. Check filter — replace if
necessary.
Temperature too low in conditioned area
Reset thermostat.
Outdoor ambient below 40 F
Install low-ambient kit.
Field-installed filter-drier restricted
Replace.
—26—