ES2 Series
Boiler Model
Input (MBH) DOE Heating Capacity (MBH) Net I=B=R Rating (MBH)
AFUE (%)
ES23
70
59
51
85
ES24
105
88
77
85
ES25
140
118
102
85
ES26
175
147
128
85
ES27
210
176
153
85
ES28
245
206
179
85
ES29
280
235
205
85
Ratings
SPECIFICATIONS
Boiler
Model
Depth Width Height Supply NPT
(inch)
Return NPT
(inch)
Vent
(inch)
Gas NPT
(inch)
Relief Valve
NPT (inch)
Drain
NPT (inch)
ES23
33
12¾
41
1¼
1¼
4
½
¾
¾
ES24
33
15½
41
1¼
1¼
5
½
¾
¾
ES25
33
18½
41
1¼
1¼
6
½
¾
¾
ES26
33
21½
41
1¼
1¼
6
½
¾
¾
ES27
33
24¾
41
1¼
1¼
7
¾
¾
¾
ES28
33
27¾
41
1¼
1¼
7
¾
¾
¾
ES29
33
30¾
41
1¼
1¼
8
¾
¾
¾
Dimensions and Connections
Electrical Requirements: 120VAC, 60 Hz, 1-ph, 15A
Boiler Model
Allowable Supply
Water Temperature
(°F)
Minimum Return
Water Temperature
(°F)
Minimum Flow
(GPM)
Waterside Pressure Drop
at 20°F DT
(Ft. of Head)
ES23
130-220
110
None
<1
ES24
130-220
110
None
<1
ES25
130-220
110
None
<1
ES26
130-220
110
None
<1
ES27
130-220
110
None
<1
ES28
130-220
110
None
<1
ES29
130-220
110
None
<1
Water Temperatures and Flows
Boiler
Model
Shipping Weight
(lbs)
Empty Weight
(lbs)
Water Content
(gal)
ES23
250
170
2
ES24
300
220
3
ES25
350
270
4
ES26
410
320
5
ES27
460
370
5
ES28
510
420
6
ES29
560
470
7
Weights and Volume