beautypg.com

Appendix d – system piping (continued) – Burnham ES2 User Manual

Page 38

background image

38

(2)

Comply with the boiler’s specific

water quality requirements. See the

Specifications Section of this manual.

(3)

Comply with the boiler’s specific

requirements for minimum water flow

through the boiler, installing a system

bypass or primary-secondary loop if

necessary to maintain flow through the

boiler when serving small zones.

3.

Overpressure

(1)

Install a properly sized expansion tank.

(2)

Do not exceed the boiler’s specific

requirements for maximum allowable

working pressure.

(3)

Do not plug or block the relief valve.

4.

Freezing

(1)

Run all portions of the system piping

inside a heated space unless the system

is properly protected with an inhibited

antifreeze solution.

5.

Overheating

(1)

Comply with the boiler’s specific

requirement for minimum water flow

through the boiler. See the

Specifications Section of this manual.

(2)

Install a low-water cutoff device

whenever the boiler is installed above

the level of the lowest heat emitter

or radiator. Also add a low-water

cutoff when required by local code

requirements.

6.

Thermal shock

(1)

Do not over-pump. Adhere to the design

flow requirements for each zone.

(2)

Install a boiler bypass, system bypass,

or primary-secondary loop when needed

to avoid returning large volumes of cold

water directly to a hot boiler.

7.

Condensation

(1)

Do not over-pump. Adhere to the design

flow requirements for each zone.

(2)

Adhere to the boiler’s specific

minimum return water and supply water

temperature requirements. Install a

boiler bypass, system bypass, or

primary-secondary loop when needed to

maintain water temperatures and flows

within the specified limits.

(3) Do not allow chilled water to enter the

boiler during the heating cycle, or heated

water to enter chilled water coils during

the cooling cycle.

8.

Dry Fire

Install a low-water cutoff when the boiler

is installed above the level of the lowest

radiator and when required by local code.

i

The following system diagrams are intended to provide a minimum level of guidance for a

successful and trouble-free installation of the boiler in common applications. They do not substitute
for proper design, evaluation, and installation by a trained and qualified installer using the proper
tools, techniques, and design expertise. Not all options are available with every boiler.

APPeNDIX D – System Piping (continued)

Hot Water Boilers, Non-Condensing

Indirect Tank?

Two or more

zones of

the same

temperature?

Two or more

zones of

different

temperatures?

Two or

more

boilers?

See

Diagram

D-W1
D-W2

D-W3 Tankless Coil
D-W4

D-W5

D-W6