DISCONNECT ELECTRICAL POWER

to the boiler and heating system before

servicing. Positively assure that no voltage is

present. Lock electrical boxes to prevent someone

from inadvertently restoring power before the

heating system is safe to operate.

NEVER DEFEAT OR JUMP OUT safety

devices.

PROTECT EACH BOILER circuit with a

properly sized over-current protection

device.

MAKE ELECTRICAL CONNECTIONS

CAREFULLY according to the boiler’s

wiring diagram and instructions

Refer to the Internal Wiring diagrams later in this

manual.

1.

Locate the wiring box on the left side of the

boiler and open the cover (Figure 7-a).

2.

Install a 120V disconnect near the boiler.

3.

Connect the 120V wiring from the disconnect

to the boiler's white (neutral), black (hot),

and green (ground) labeled "120VAC Power

supply". Do not reverse polarity.

4.

Connect the 120V wiring from the circulator

to the white (neutral) yellow (hot) wires

marked "circulator".

WIRE AN ADDITIONAL SAFETY LIMIT

such as a low water cutoff or temperature

limit device, other than an IQ

™ Control device,

in series with the 120V circuit used to power the

boiler. Do not alter the boiler’s factory wiring when

adding an additional limit.

. CONNECT ELECTRICAL WIRING

5.

Connect the 24V wiring from the thermostat

to the "T-T" terminals on the Option Control

Panel.

6.

To connect other external devices, refer to

the instructions included with these devices.