If "Err" IS displayed on the IQ Boiler Control: "Err" flashes on the IQ Boiler control display followed

by a number. Use the following table along with this error number to determine the problem and possible

causes:

IQ Boiler Control Error Codes (when

"Err"

is flashing)

Display

Status

Boiler / Control Action(s)

Blank

Boiler and Circulator off No 120 Vac power at boiler, check breaker and wiring between breaker panel and boiler.

Err

4

Flame Current Lower

than Threshold

Check pilot assembly.

Err

6

Flame Sensed Out of

Normal Sequence

Flame sensed out of normal sequence (before opening gas valve or after closing gas

valve).

Err

18

Electronics Failure

Replace Control .

Err

24

Flame Sensed During

Post-Purge

Flame sensed during post-purge (after gas valve signaled closed).

Err

32

Temperature Sensor

Failure

Temperature sensor or interface failure (open or short connection, increased connection

resistance, dual sensor mismatch) or control hardware failure.

Err

55

Damper Failed

to Open

Atmospheric Damper End Switch failed to close (end switch contacts stuck open).

Err

56

Damper Failed to Close Atmospheric Damper End Switch failed to open (end switch contacts stuck closed).

Err

57

Flame Rod Shorted to

Burner Ground

Flame Rod shorted to burner ground, this can result from excessive flue gas

condensation.

Err

58

AC Line Frequency Error AC Signal is too noisy or frequency is incorrect.

Err

59

Line Voltage Error

AC voltage out of specification high or low.

Err

60

Thermostat Input Higher

than Threshold

Check thermostat wiring.

Err

61

Line Voltage Unstable

Possibly too many heavy loads switching on and off cause erratic supply voltage.

Err

63

Soft Lockout - Maximum

Recycles Exceeded

Maximum number of recycles exceeded.

Err

64

Soft Lockout - Internal

Failure

Caused by general electronics failure such as relay open or shorted contacts, flame

sensing circuit error, or A to D error.

tRoUBLeShootING (continued)

IQ Boiler Control Status Codes (when

"Err"

is not displayed) - continued

Display

Status

Boiler / Control Action(s)

20

Damper Failed

Open

The damper end switch has not closed (damper end switch is open) at the beginning of

the heat cycle. An alarm message is sent but the control is not in lockout.

21

Damper Failed

Closed

The damper end switch has not opened (damper end switch is closed) at the

beginning of the heat cycle. An alarm message is sent but the control is not in lockout.