APPENDIX C – GAS PIPING

ASSURE GAS PIPING IS LEAK FREE

AND OF PROPER SIZE and type for the

connected load.

SHUT OFF MAIN GAS SUPPLY prior to

installing or servicing boiler gas piping.

1.

Determine the boiler’s maximum gas

demand and minimum gas supply pressure

(printed on the boiler’s rating label) and the

demand of other gas appliances served by

the same gas meter.

2.

Ensure that gas piping, fittings, and gas

meter capacities can supply the maximum

gas demand of all appliances at pressures

above their minimum allowable gas

pressure. Tables C-1 and C-2 provide typical

capacities of gas pipes and fittings.

3.

Derate the gas flow through pipes by

multiplying by a correction factor in Table

C-3 based on the specific gravity of the gas.

4.

For materials or conditions other than those

listed above, refer to the National Fuel Gas

Table C-1: Maximum Capacity of Schedule 40 Pipe in Cubic Feet Per Hour (CFH)

*

Length

(Feet)

0.3” w.c. Pressure Drop

0.5” w.c. Pressure Drop

½

¾

1

½

¾

1

10

132

278

520

1050

175

360

680

1400

20

92

190

350

730

120

250

465

950

30

73

152

285

590

97

200

375

770

40

63

130

245

500

82

170

320

660

50

56

115

215

440

73

151

285

580

60

50

105

195

400

66

138

260

530

70

46

96

180

370

61

125

240

490

80

43

90

170

350

57

118

220

460

90

40

84

160

320

53

110

205

430

100

38

79

150

305

50

103

195

400

*

1 CFH of Natural Gas is approximately equal to 1000 BTU/hr; 1 CFH of LP is approximately equal to 2500 BTU/hr.

Table C-2: Equivalent Lengths (ft) Of Standard Pipe Fittings & Valves

Pipe

Size

Gate

Globe

Angle

Swing

Check

90°

Elbow

45°

Elbow

90° ‘T’, Flow

Through Run

90° ‘T’, Flow

Through Branch

½”

0

19

9

4

2

1

1

3

¾”

0

23

12

5

2

1

1

4

1”

1

29

15

7

3

1

2

5

1 ¼”

1

39

20

9

4

2

2

7

1 ½”

1

45

22

11

5

3

3

8

Code, NFPA54/ANSI Z223.1, or size the

system using standard engineering methods

acceptable to authority having jurisdiction.

USE PROPER THREAD COMPONENTS

on all gas connectors.

USE THREAD (JOINT) COMPOUNDS

(pipe dope) rated for liquefied petroleum

gas.

Table C-3: Specific Gravity Correction Factors For

Natural Gas

Specific

Gravity

Correction

Factor

Specific

Gravity

Correction

Factor

0.50

1.10

0.85

0.81

0.55

1.04

0.90

0.82

0.60

1.00

1.00

0.78

0.65

0.96

1.10

0.74

0.70

0.93

1.20

0.71

0.75

0.90

1.30

0.68

0.80

0.87

1.40

0.66