25— condenser only ratings – Bryant 593C User Manual
Page 25
—25—
CONDENSER ONLY RATINGS*
See notes on page 26.
SST
°F
CONDENSER ENTERING AIR TEMPERATURES °F
55
65
75
85
95
105
115
593C018-C, D
TCG
17.9
16.6
15.3
14.0
12.7
11.3
10.0
30
SDT
75.7
84.2
93.0
102.0
111.0
120.0
129.0
KW
1.10
1.18
1.26
1.33
1.39
1.44
1.46
TCG
19.8
18.5
17.1
15.7
14.3
12.9
11.5
35
SDT
77.7
86.2
94.8
104.0
112.0
121.0
130.0
KW
1.13
1.22
1.30
1.38
1.45
1.51
1.55
TCG
21.8
20.5
19.0
17.6
16.1
14.6
13.1
40
SDT
79.9
88.3
96.8
105.0
114.0
123.0
132.0
KW
1.15
1.25
1.34
1.43
1.51
1.58
1.64
TCG
24.0
22.6
21.0
19.5
17.9
16.4
14.8
45
SDT
82.3
90.4
98.9
107.0
116.0
125.0
134.0
KW
1.18
1.28
1.38
1.48
1.57
1.65
1.72
TCG
26.3
24.8
23.2
21.6
19.9
18.2
16.6
50
SDT
84.9
92.8
101.0
110.0
118.0
127.0
135.0
KW
1.20
1.31
1.42
1.53
1.63
1.72
1.80
TCG
28.6
27.1
25.4
23.7
22.0
20.2
18.5
55
SDT
87.6
95.3
103.0
112.0
120.0
129.0
137.0
KW
1.23
1.35
1.46
1.58
1.69
1.79
1.88
593C024-C, D
TCG
24.0
22.3
20.5
18.7
16.9
15.1
13.3
30
SDT
81.3
89.8
98.6
108.0
117.0
126.0
136.0
KW
1.52
1.63
1.73
1.81
1.88
1.93
1.96
TCG
26.6
24.8
22.9
21.0
19.2
17.3
15.4
35
SDT
83.6
91.9
101.0
109.0
118.0
127.0
137.0
KW
1.57
1.68
1.79
1.89
1.97
2.04
2.08
TCG
29.4
27.5
25.5
23.5
21.5
19.5
17.6
40
SDT
86.2
94.3
103.0
111.0
120.0
129.0
138.0
KW
1.61
1.74
1.86
1.97
2.06
2.14
2.20
TCG
32.3
30.3
28.2
26.1
24.0
21.9
19.8
45
SDT
88.9
96.8
105.0
114.0
122.0
131.0
140.0
KW
1.66
1.79
1.92
2.05
2.15
2.25
2.32
TCG
35.3
33.2
31.1
28.8
26.6
24.4
22.2
50
SDT
92.0
99.5
108.0
116.0
124.0
133.0
141.0
KW
1.71
1.85
1.99
2.12
2.25
2.35
2.44
TCG
38.4
36.3
34.1
31.7
29.4
27.0
24.7
55
SDT
95.3
102.0
110.0
118.0
127.0
135.0
144.0
KW
1.76
1.91
2.06
2.20
2.34
2.46
2.56
593C030-C, D
TCG
30.2
27.9
25.6
23.4
21.3
19.3
17.3
30
SDT
81.3
90.5
99.8
109.0
118.0
128.0
137.0
KW
1.88
2.02
2.15
2.27
2.36
2.44
2.50
TCG
33.5
31.0
28.6
26.3
24.0
21.8
19.7
35
SDT
83.4
92.5
102.0
111.0
120.0
129.0
139.0
KW
1.93
2.09
2.24
2.37
2.48
2.57
2.65
TCG
37.1
34.4
31.8
29.3
26.8
24.5
22.2
40
SDT
85.7
94.7
104.0
113.0
122.0
131.0
140.0
KW
1.99
2.16
2.32
2.47
2.59
2.70
2.79
TCG
40.8
38.0
35.2
32.5
29.8
27.3
24.8
45
SDT
88.1
97.0
106.0
115.0
124.0
133.0
142.0
KW
2.04
2.23
2.41
2.57
2.71
2.84
2.94
TCG
44.8
41.7
38.8
35.9
33.0
30.3
27.6
50
SDT
90.7
99.5
108.0
117.0
126.0
135.0
144.0
KW
2.09
2.29
2.49
2.67
2.83
2.97
3.09
TCG
49.0
45.7
42.6
39.5
36.4
33.5
30.6
55
SDT
93.5
102.0
111.0
120.0
129.0
137.0
146.0
KW
2.14
2.36
2.57
2.77
2.94
3.10
3.25
593C036-C, D
30
TCG
35.9
33.4
30.9
28.4
25.9
23.4
21.0
SDT
80.5
89.7
98.9
108.0
118.0
127.0
136.0
KW
2.20
2.38
2.55
2.70
2.82
2.93
3.00
35
TCG
39.7
37.1
34.4
31.7
29.1
26.5
23.9
SDT
82.6
91.6
101.0
110.0
119.0
128.0
138.0
KW
2.25
2.45
2.64
2.80
2.95
3.07
3.17
40
TCG
43.8
41.0
38.1
35.3
32.5
29.7
27.0
SDT
84.8
93.7
103.0
112.0
121.0
130.0
139.0
KW
2.30
2.52
2.72
2.91
3.08
3.22
3.34
45
TCG
48.1
45.1
42.1
39.1
36.1
33.1
30.2
SDT
87.2
96.0
105.0
114.0
123.0
132.0
141.0
KW
2.35
2.59
2.81
3.02
3.20
3.37
3.51
50
TCG
52.6
49.5
46.3
43.1
39.9
36.7
33.6
SDT
89.7
98.4
107.0
116.0
125.0
134.0
143.0
KW
2.40
2.66
2.90
3.12
3.33
3.52
3.68
55
TCG
57.4
54.0
50.7
47.3
43.9
40.5
37.2
SDT
92.4
101.0
110.0
119.0
127.0
136.0
145.0
KW
2.45
2.72
2.98
3.23
3.46
3.66
3.85