Provisioning, Provisioning defaults, Table 4 – ADTRAN 3010 NTU-8 User Manual
Page 12
Total Access 3000/3010 NTU-8 Single Fiber Quad E1 Installation and Maintenance Practice
6
61182301E1-5A
PROVISIONING
The NTU-8F is automatically configured to match the LTU-8 settings and does not require local
provisioning. Provisioning for the LTU-8 is via the Total Access 3000/3010 System Controller
Unit (SCU). The SCU initiates and controls the transfer of commands and data to and from the
LTU-8. The LTU-8 generates all menu items for both the LTU-8 and the NTU-8F. The LTU-8
retains provisioning data in a nonvolatile memory device in the event of power loss.
Viewing of all provisionable settings, status, and Performance Monitoring menus are supported
from the NTU-8F local craft port, labeled
CRAFT
, but changes cannot be made. The craft port is
a DB-9 connector that supplies an RS-232 interface for connection to a controlling terminal.
The supported terminal type is VT100 or compatible and is set for the following:
• 38400 bps
• 8-data bits
• no parity
• no flow control
• 1-stop bit
Y-Modem flash upgrade is password protected from the NTU-8F. The default password is
“password,” which can be changed from the NTU-8F.
Provisioning Defaults
On initial installation, the NTU-8F is set to factory default provisioning options.
available options, with the default settings shown in bold type.
Table 4. Provisioning Defaults
NTU-8F
Settings
Defaults
Card Service State
In Service;
Out of Service-Maintenance;
Out of Service Unassigned
Out of Service-Maintenance
NTU Push Buttons
Disabled;
Enabled
Disabled
External Alarms
Disabled;
Enabled
Disabled
Change NTU Firmware
Upgrade Password
password
password
Port Service State
In Service;
Out of Service-Maintenance;
Out of Service-Unassigned
Out of Service-Maintenance
E1 Frame Format
FAS;
FAS+CRC4
FAS
E1 Data Rate
0h - FFh
FFh
Timeslot Idle Pattern
00h - FFh
FFh