Operation – Operation Modes
14
Smart-UPS® VT ISX 20-30 kVA, 200 V Operation
990-2818A
Turn into mechanical bypass using the mechanical bypass lever
From the Main Menu, select Control and press ENTER.
Use UP/DOWN key to navigate to UPS into Bypass and press ENTER.
Use UP/DOWN key to navigate to YES, confirm UPS into bypass, and press ENTER.
Open the UPS front door.
Turn the mechanical bypass lever upwards to activate the internal mechanical bypass switch.
The load will now be supported directly by utility power.
Caution
The load is not protected by the UPS when the internal mechanical bypass system is
active, and, the power is not conditioned.
Note
If the UPS is running and controllable through the display, carry out steps 1 through 6.
If not, go directly to step 4.
Control
Status
Setup
Logging
Display
Diags
Help
Main Menu
su
o0
30
8a
- 5000VA (25 pages)
- MX28B-400 (46 pages)
- CTEG4-240MB-5 (7 pages)
- 200/208 V (52 pages)
- VS 100 (54 pages)
- SMARTUPS 700 (60 pages)
- AP7562J (24 pages)
- 100VAC (18 pages)
- Smart-UPS VT (56 pages)
- 1400XLT (30 pages)
- 350/550 (2 pages)
- SURTA1500XLJ (16 pages)
- RT-UXI (20 pages)
- 2200 VA (17 pages)
- 208 Vac (17 pages)
- 1500VA (18 pages)
- 60-80kW 208/480V (34 pages)
- 420 (3 pages)
- 220 VAC (21 pages)
- 350 (2 pages)
- AP9215 (20 pages)
- Back-UPS CS 500 (2 pages)
- PDU (54 pages)
- Airless Paint Sprayer 68001 (24 pages)
- AP7610 (16 pages)
- AP7902 AP7911 (26 pages)
- UPS (2 pages)
- RT XLI/XLICH (34 pages)
- 990-2233A (19 pages)
- 208/220 (48 pages)
- NS 600 (2 pages)
- SYMF800KH (54 pages)
- 20-30 kVA 480V (4 pages)
- 100 VAC (25 pages)
- 750 (17 pages)
- 3000 (23 pages)
- MX28B200 (61 pages)
- RS 1000 (2 pages)
- 200-240 VAC (21 pages)
- 5000RMB (23 pages)
- 480kW400V (32 pages)
- AP9825I (1 page)
- 250/450 (2 pages)
- SUA48RMXLBP3U (8 pages)