8 faults, Faults – WIKA DI35 User Manual
Page 48
8 Faults
48
WIKA operating instructions digital indicator DI35-M
8 Faults
Error description
Measures/Solutions
The unit permanently indicates
overflow „ ¯ ¯ ¯ ¯ ¯ “.
(5 bars at the top of the 7 segment
display)
The input has a very high
measurement, check the
measuring circuit.
With a selected input with a low
voltage signal, it is only connected
on one side or the input is open.
Not all of the activated setpoints
are parameterised. Check if the
relevant parameter PN1, PN2,
PN100…PN130 are adjusted
correctly.
The unit permanently shows
underflow „ _ _ _ _ _ “.
(5 bars at the bottom of the 7
segment display)
The input has a very low
measurement, check the
measuring circuit .
With a selected input with a low
voltage signal, it is only connected
on one side or the input is open.
Not all of the activated setpoints
are parameterised. Check if the
relevant parameter PN1, PN2,
PN100…PN130 are adjusted
correctly.
The word "HELP " lights up in the 7-
segment display.
The unit has found an error in the
configuration memory. Perform a
reset on the default values and
reconfigure the unit according to
your application.
Program numbers for parameterising
of the input are not accessible.
The programming lock is set at a
user level that does not allow
access.
Under PN1, a different sensor type
was parameterised so that the
desired program number cannot
be parameterised.
"Err1" lights up in the 7-segment
display
Please contact the manufaturer if
errors of this kind occur.
The addressed digital input does not
react.
Measure the current of the digital
input with a multimeter. It should
be between 1 mA and 3 mA.
Program numbers for the analog
output PN20…PN22 are not
The analog output is an option of
this device type. If it is not