6 Commissoning, operation
WIKA operating instructions digital indicator model DI35-M
43
PN
Function
Range of values
De-
fault
User-
level
1 = transmission operation
Security settings
50
Programming lock
0000…9999
0000
8
51
Authorization code
0000…9999
0000
0
52
Userlevel
0…8
8
0
Flashing of the LED display
59
Display flashing (approx.
0.5 seconds)
No flashing
Flashing at set point 1
Flashing at set point 2
Flashing at set point 3
Flashing at set point 4
Flashing at set point 1 and 2
Flashing at set point 3 and 4
Flashing at set point 1, 2, 3
and 4
0 = no flashing
1 = flashes at 1
2 = flashes at 2
3 = flashes at 3
4 = flashes at 4
5 = flashes at 1 and 2
6 = flashes at 3 and 4
7 = flashes at 1, 2, 3 and 4
0
6
Setpoint 1
60
Setpoint 1 (Source / Trigger
value)
0 = not activated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = sliding average value
6 = totalizer value
7 = absolute value
1
6
61
Threshold
-9999…99999
1000
6
62
Hysteresis
1…99999
1
6
63
Active above / below SP
value
0 = active below SP
1 = active above SP
1
6
64
Switch delay
0.0…10.0 seconds
0,0
6
65
Delay type
0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on/-off delay
4 = suppression with activated
digital input
1
6
67
Setpoint confirmation
0 = no locking
1 = switch-off locking by multi-
function key
2 = switch-off locking by
external input
3 = switch-off locking by both
4 = no locking
5 = switch-on locking by multi-
function key
6 = switch-on locking by digital
input
7 = switch-on locking by both
0
6