3 Specifications
WIKA operating instructions digital indicator model DI35-M
11
Accuracy of input signals
Input
signals
Measuring span
Measuring error in % of
the span
Inner
resistance
Current signals
0…20 mA ± 0.02 % ± 1 Digit
50
Ω
4…20 mA ± 0.02 % ± 1 Digit
50
Ω
0…5 mA ± 0.02 % ± 1 Digit
50
Ω
0…2 mA ± 0.02 % ± 1 Digit
50
Ω
Voltage signals
-1…10 V ± 0.01 % ± 1 Digit
150 kΩ
-1…5 V ± 0.02 % ± 1 Digit
150 kΩ
-500…2500 mV ± 0.03 % ± 1 Digit
1 MΩ
-500…1250 mV ± 0.03 % ± 1 Digit
1 MΩ
-500…600 mV ± 0.03 % ± 1 Digit
1 MΩ
-300…300 mV ± 0.03 % ± 1 Digit
1 MΩ
-150…150 mV ± 0.03 % ± 1 Digit
1 MΩ
-75…75 mV ± 0.04 % ± 1 Digit
1 MΩ
-35…35 mV ± 0.06 % ± 1 Digit
1 MΩ
-18…18 mV ± 0.03 % ± 1 Digit
1 MΩ
PT100 (2-/3-/4-wire)
-200,0…850,0 °C ± 0.04 % ± 1 Digit
1 MΩ
Thermocouple
Typ L
-200…900 °C ± 0.06 % ± 1 K
1 MΩ
Typ J
-210…1200 °C ± 0.05 % ± 1 K
1 MΩ
Typ K
-250…1271 °C ± 0.05 % ± 1 K
1 MΩ
Typ B
-100…1810 °C ± 0.10 % ± 1 K
1 MΩ
Typ S
0…1767 °C ± 0.06 % ± 1 K
1 MΩ
Typ N
-250…1300 °C ± 0.06 % ± 1 K
1 MΩ
Typ E
-260…1000 °C ± 0.06 % ± 1 K
1 MΩ
Typ R
0…1767 °C ± 0.07 % ± 1 K
1 MΩ
Typ T
-240…400 °C ± 0.07 % ± 1 K
1 MΩ
Resistance (2-/3-/4-wire)
100 Ω ± 0.04 % ± 1 Digit
1 MΩ
1 kΩ ± 0.04 % ± 1 Digit
1 MΩ
10 kΩ ± 0.04 % ± 1 Digit
1 MΩ
The measuring errors are valid for ambient temperatures of 20…40 °C and a
measuring time of 1 second.
The datas for PT100 3-/4-wire are valid for a max. resistance of wire of 10
Ω.