WIKA DI35 User Manual
Page 44

6 Commissoning, operation
44
WIKA operating instructions digital indicator DI35-M
PN
Function
Range of values
De-
fault
User-
level
Setpoint 2
70
Setpoint 2 (Source / Trigger
value)
0 = not activated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = sliding average value
6 = totalizator value
7 = absolute value
1
6
71
Threshold
-9999…99999
1000
6
72
Hysteresis
1…99999
1
6
73
Active above / below SP
value
0 = active below SP
1 = active above SP
1
6
74
Switch delay
0.0…10.0 seconds
0,0
6
75
Delay type
0 = none
1 = switch-on delay
2 = switch-off delay
3 = switch-on / -off delay
4 = suppression with activated
digital input
1
6
77
Setpoint confirmation
0 = no locking
1 = switch-off locking by multi-
function key
2 = switch-off locking by
external input
3 = switch-off locking by both
4 = no locking
5 = switch-on locking by multi-
function key
6 = switch-on locking by digital
input
7 = switch-on locking by both
0
6
Setpoint 3
80
Setpoint 3 (Source / Trigger
value)
0 = not activated
1 = instantaneous value
2 = MIN value
3 = MAX value
4 = HOLD value
5 = sliding average value
6 = totalizator value
7 = absolute value
1
6
81
Threshold
-9999…99999
1000
6
82
Hysteresis
1…99999
1
6
83
Active above / below SP
value
0 = active below SP
1 = active above SP
1
6
84
Switch delay
0.0…10.0 seconds
0,0
6