6 Commissoning, operation

WIKA operating instructions digital indicator model DI35-M

41

PN

Function

Range of values

De-
fault

User-
level

41 = ± 75 mV
42 = ± 35 mV
43 = ± 18 mV
44 = 0…5 mA
45 = 0…2 mA

1

Final value / Fullscale

PN20 ≤ 12 or PN0 ≥ 30

-9999…99999

10000

2

2

Zero point / Offset

PN0 ≤ 12 and PN0 ≥ 30

-9999…99999

0

2

3

Decimal point
Voltage, current

With PN0 ≤ 12

and PN0 ≥ 30
PTxxx resistance
thermometer

Physical unit and number
after the decimal point; with
PN0 = 13 to 20

0 or 1: the physical unit is not
shown in the display
2 to 5: the unit is shown after
the figure
Thermocouple
Physical unit and number
after the decimal point;
PN0 = 21 to 29

0 or 1: the physical unit is not
shown in the display


00000…0,0000


0 = 8888.8 [°C]
1 = 8888.8 [°F]
2 = 8888°C [°C]
3 = 8888°F [°F]
4 = 888.8°C [°C]
(-99.9…999.9)
5 = 888.8°F [°F]
(-99.9…999.9)

0 = 8888.8 [°C]
1 = 8888.8 [°F]
2 = 8888°C [°C]
3 = 8888°F [°F]


none


2


2


2

5

Offset shift
At analogue or resistance
measurements and sensor
calibration PN0 = 1 to 12 or
30 to 45,
with temperature sensors,
PN0 = 13 to 29


-9999…99999



Measuring range


0



0 / 0,0


2



2

6

thermocouple reference
junction
With PN0 = 21 to 29 (can
only be parameterised with
thermocouples)

0 = inactive
1 = active

1

2

7

Setpoint for taring

-9999…99999

0

2

8

Activator for taring

0 = none
1 = digital input
2 = multi-function key
3 = digital input without key
4 = boot-up
5 = combination 1 with 4
6 = combination 2 with 4
7 = combination 3 with 4

0

2