WIKA operating instructions level switch model LSD-30

GB

Error

Description

ATT1

On changing the switch point, the system automatically reduces the reset point.

ATT3

Password entered for menu access is incorrect.

ERR

Internal error

OL

Sensor burnout

UL

Sensor short-circuit

Acknowledgement of an error display by pressing the "Enter" key.

Problem

Possible cause

Measure

No output signal

Cable break

Check the continuity

No output signal/line break

Mechanical load too high

Replace sensor with a suitable design

No output signal

No/wrong power supply

Rectify the power supply

No/wrong output signal

Wiring error

Observe the pin assignment

Constant output signal upon

change in level

Specific gravity of the medium too low

Float jammed or damaged

Check the float for adjustment to specific

gravity

Check the output signal. Check the

instrument for contamination or defects

Signal span too small

Power supply too high/low

Rectify the power supply

Signal span drops

Moisture has entered

Assemble the cable correctly

Output signal not proportional to

the level

Specific gravity range of the float not

suitable

Check the S.G. specifications for the

float

Output signal interference

Outer magnetic field

Remove source of interference

If complaint is unjustified, we will charge you the complaint processing fees.

CAUTION!

If faults cannot be eliminated by means of the measures listed above, the instrument must

be shut down immediately, and it must be ensured that signal is no longer present, and it

must be prevented from being inadvertently put back into service. In this case, contact the

manufacturer. If a return is needed, follow the instructions given in chapter 9.2 "Return".