WIKA operating instructions level switch model LSD-30

GB

11613033.01 01/2012 GB/D/F/E

6.4 Switching functions

Hysteresis function

If the level fluctuates around the set point, the hysteresis keeps

the switching status of the outputs stable. With increasing level,

the output switches when reaching the switch point (SP).

Contact normally open (HNO): active

Contact normally closed (HNC): inactive

With the level falling again, the output will not switch back before

the reset point (RP) is reached.

Contact normally open (HNO): inactive

Contact normally closed (HNC): active

Window function

The window function allows for the control of a defined range.

When the level is between window High (FH) and window Low

(FL), the output switches on.

Contact normally open (FNO): active

Contact normally closed (FNC): inactive

When the level is outside window High (FH) and window Low

(FL), the output does not switch on.

Contact normally open (FNO): inactive

Contact normally closed (FNC): active