WIKA Betriebsanleitung Temperatur-Transmitter T53

T53.10.0IS

Class I, Zone O, Ex ia IIC oder Ex iaD, FISCO

P

o

< 0,84 W P

o

< 1,3 W FISCO systems FISCO systems

U

i

30 VDC

30 VDC

17.5 VDC

15 VDC

l

i

120 mA DC 300 mA DC 250 mA DC

P

i

0,84 W

1,3 W

2,0 W

L

i

1 µH

1 µH

1 µH

1 µH

C

i

2,0 nF

2,0 nF

2,0 nF

2,0 nF

T1 ... T4 T

a

< 85 °C T

a

< 75 °C T

a

< 85 °C

T

a

< 85 °C

T5

T

a

< 70 °C T

a

< 65 °C T

a

< 60 °C

T

a

< 60 °C

T6

T

a

< 60 °C T

a

< 45 °C T

a

< 45 °C

T

a

< 45 °C

T53.10.0IS

Class I, Zone 1, Ex ib IIC, FISCO

P

o

< 0,84 W

FISCO systems

U

i

30 VDC

17,5 VDC

l

i

250 mA DC

P

i

5,32 W

L

i

1 µH

1 µH

C

i

2,0 nF

2,0 nF

T1 ... T4

T

a

< 85 °C

T

a

< 85 °C

T5

T

a

< 75 °C

T

a

< 55 °C

T6

T

a

< 60 °C

T

a

< 60 °C

Montagehinweise

Die galvanische Trennung zwischen dem Sensorstromkreis und der

Eingangsbeschaltung ist nicht unfehlbar. Allerdings ist die galvani-

sche Trennung zwischen den Kreisen so ausgelegt, dass diese eine

Testspannung von AC 500 V für eine Minute aushält.

In einem Bereich, der möglicherweise durch Gase gefährdet ist,

muss der Transmitter in einem Gehäuse montiert werden, das

mindestens der Schutzart IP 20 gemäß EN 60 529 entspricht.