11178648.04 03/2010 GB/D/F/E

10

WIKA Operating Instructions Temperature Transmitter T53

T53.10.0IS

Class I, Zone O, Ex ia IIC or Ex iaD, FISCO

P

o

< 0.84 W P

o

< 1.3 W FISCO systems FISCO systems

U

i

30 VDC

30 VDC

17.5 VDC

15 VDC

l

i

120 mA DC 300 mA DC 250 mA DC

P

i

0.84 W

1.3 W

2.0 W

L

i

1 µH

1 µH

1 µH

1 µH

C

i

2.0 nF

2.0 nF

2.0 nF

2.0 nF

T1 ... T4 T

a

≤ 85 °C T

a

≤ 75 °C T

a

≤ 85 °C

T

a

≤ 85 °C

T5

T

a

≤ 70 °C T

a

≤ 65 °C T

a

≤ 60 °C

T

a

≤ 60 °C

T6

T

a

≤ 60 °C T

a

≤ 45 °C T

a

≤ 45 °C

T

a

≤ 45 °C

T53.10.0IS

Class I, Zone 1, Ex ib IIC, FISCO

P

o

< 0.84 W

FISCO systems

U

i

30 VDC

17.5 VDC

l

i

250 mA DC

P

i

5.32 W

L

i

1 µH

1 µH

C

i

2.0 nF

2.0 nF

T1 ... T4

T

a

≤ 85 °C

T

a

≤ 85 °C

T5

T

a

≤ 75 °C

T

a

≤ 75 °C

T6

T

a

≤ 60 °C

T

a

≤ 60 °C

Installation instructions

The sensor circuit is not infallibly galvanically isolated from the Field-

bus input circuit. However, the galvanic isolation between the circuits

is capable of withstanding a test voltage of AC 500 V during 1 minute.

In a potentially explosive gas atmosphere, the transmitter shall be

mounted in an enclosure in order to provide a degree of protection of

at least IP 20 according to EN 60 529.