Appendix 1: fm-csa installation drawing – WIKA T53 User Manual

Page 26

background image

GB

11178648.04 03/2010 GB/D/F/E

26

WIKA Operating Instructions Temperature Transmitter T53

Sensor

Sensor

Sensor

Model T53.10.0IS

Approved

Termina-

tion

Terminal 3, 4, 5, 6

V

t

or U

o

: 5.71 V

l

t

or l

o

:

8.4 mA

P

t

or P

o

: 12 mW

C

a

or C

o

: 40 µF

L

a

or L

o

: 200 mH

The device must not be

connected to any

associated apparatus

which uses or generates

more than 250 VRMS

Associated Apparatus

Barrier with

entity Parameters:

Unclassified Location

UM ≤ 250 V

V

oc

or U

o

≤ V

max

or U

i

l

sc

or l

o

≤ l

max

or l

i

P

o

≤ P

i

C

a

or C

o

≥ C

i

+ C

cable

L

a

or L

o

≥ L

i

or L

cable

or

FISCO Supply

Class I, Division 2, Groups A, B, C, D

or

Class I, Zone 1, IIC

Hazardous (classified) Location

Entity Parameters

Terminal 1, 2

Class I, Zone 1, Ex ib IIC

Entity/FISCO

Barrier type Rectangular

barrier

FISCO

Segment

coupler

T1 ... T4

Ta ≤ +85 °C Ta ≤ +85 °C

T5

Ta ≤ +75 °C Ta ≤ +75 °C

T6

Ta ≤ +60 °C Ta ≤ +60 °C

V

max

/ Ui

30 V

17.5 V

l

max

or li

250 mA

any

Pi

5.32 W

any

Ci

2.0 nF

2.0 nF

Li

1 µH

1 µH

See Installation notes.

Installation Drawing 11175631.01

2/6

Nonincendive Field Wiring

parameters

Terminal 1, 2

NI, Class I, Division 2, Group A, B, C, D

NIFW/FNICO

T1 ... T4

Ta ≤ +85 °C Ta ≤ +75 °C

T5

Ta ≤ +75 °C Ta ≤ +65 °C

T6

Ta ≤ +60 °C Ta ≤ +45 °C

V

max

/ Ui

30 V

17.5 V

Pi

5.32 W

any

Ci

2.0 nF

2.0 nF

Li

1 µH

1 µH

For a current-controlled circuit the

parameter l

max

is not required and

need not be aligned with the parameter

l

sc

or l

t

of the barrier or associated

nonincendive field wiring apparatus.

Appendix 1: FM-CSA Installation Drawing