3. Specifications

Electrical data

Power supply U

B

DC V

12 < U

B

≤ 30

Influence of power

supply

% FS/10 V

≤ 0.1

Permissible residual

ripple

% ss

≤ 10

Output signal

Variant 1

Variant 3

Variant 4

4 … 20 mA, 2-wire, passive, per NAMUR NE 43

0 ... 20 mA, 3-wire

0 ... 10 V, 3-wire

Permissible max. load R

A

for variant 1 - 3

R

A

≤ (U

B

- 12 V)/0.02 A with R

A

in Ohm and U

B

in

Volt, however max. 600 Ω

Effect of load

(variant 1 - 3)

% FS

≤ 0.1

Electrical zero point

through a jumper across terminals 5 and 6 (see

operating instructions)

Long-term stability of

electronics

% FS/a

< 0.3

Electr. output signal

≤ 2.5 % of the measuring span (option ≤ 1.6 %)

Linearity

% of span

≤ 2.5 % (option ≤ 1.6 %), terminal method

Electrical connection

via angular connector, 180° rotatable, wire

protection, cable gland M20 x 1.5, incl. strain relief,

connection cable: Outer diameter 7 ... 13 mm,

conductor cross-section 0.14 ... 1.5 mm

2

,

temperature resistance up to 70 °C

Ingress protection

Angular connector: IP 65 per EN 60529 / IEC 60529

EMC directive

2007/108/EC interference emission (limit class B)

and immunity to EN 61 326-1

As a power supply, an unstabilised DC power supply is sufficient in the range of

the specified limits. It is important to ensure that the applied power supply is at

least greater than the maximum required voltage drop from the external display

and evaluation units; i.e. the voltage at the pressure transmitter must not fall

below 10 V.