1 setting the machine number, 2 setting the line termination, Setting the machine number – Kramer Electronics VS-121HC User Manual
Page 14: Setting the line termination, Figure 5: master/slave configuration
Operating the VS-121HC Switcher/Transcoder
11
7.3.1 Setting the Machine number
Set the first or master device to machine #1. Set all other devices to other
unique machine numbers, as defined in
7.3.2 Setting the Line Termination
To ensure correct operation, the RS-485 line must be terminated at both
ends. The master unit may be located at any part of the line, but when it is at
the end of the line, the termination switch must be set ON.
To set line termination, as shown in
• For the VS-121HC units located at the ends of the RS-485 line (whether
master or slave), set DIP 8 ON
• For all other VS-121HC units in the middle of the line, set DIP 8 OFF
Figure 5: Master/Slave Configuration