Operating the VS-121HC Switcher/Transcoder

11

7.3.1 Setting the Machine number

Set the first or master device to machine #1. Set all other devices to other
unique machine numbers, as defined in

Table 4

.

7.3.2 Setting the Line Termination

To ensure correct operation, the RS-485 line must be terminated at both
ends. The master unit may be located at any part of the line, but when it is at
the end of the line, the termination switch must be set ON.

To set line termination, as shown in

Figure 5

:

• For the VS-121HC units located at the ends of the RS-485 line (whether

master or slave), set DIP 8 ON

• For all other VS-121HC units in the middle of the line, set DIP 8 OFF

Figure 5: Master/Slave Configuration