resulting voltage must be set high enough to hold the relay closed under all
shock and vibration conditions the vehicle will be subjected to. Low settings
minimize the current required to power the coil, thereby reducing coil heating
and increasing battery life.

Values for

AUX HOLDING

should be determined with specifications or advice

from the relay or brake manufacturer.

Example: To use a 24V brake in a 48V vehicle, try

AUX PULL IN

= 2 (28.8V)

AUX HOLDING

= 3 (16.8V)

EMB DELAY
The electromagnetic brake dropout delay sets a delay time before the EM
brake drops. The delay countdown begins either (1) when the vehicle has come
to rest and the main contactor has opened or (2) during field braking, when
the vehicle has slowed below the

FLD BRK SPD

.

Related parameter: The

FLD BRAKE

parameter defines when the EM brake

delay will begin—see (1) and (2) above.

EMB SPD CHECK
The electromagnetic brake speed check parameter adds extra measures to
prevent the locking of the EM brake at high vehicle speeds under conditions
when the main contactor is open (for example, if the keyswitch is turned off
during driving or a fault is detected). When it is enabled, the controller over-
rides the

EMB DELAY

in an attempt to allow the vehicle to slow down prior to

engaging the EM brake.

EMB SPD VALUE
The electromagnetic brake at speed value parameter sets the speed at which
the EM brake is permitted to lock. It is programmable from 0 to 40.0 mph,
and is typically set at the extreme low end of that range. The purpose of

EMB

SPD VALUE

is to prevent dropping the EM brake at high speed, which could be

dangerous on certain terrain (e.g., wet grass).

In the event of main contactor failure (or fault detection that commands

the contactor to open) the EM brake parameters control the brake as follows.

EMB SPD CHECK

= off

EM brake driver will turn off after

EMB DELAY

time has expired.

EMB SPD CHECK

= on

EM brake driver will not turn off until vehicle speed is detected
as having reduced to the set

EMB SPD VALUE

.

If

EMB SPD VALUE

is set below 1.0 mph, the EM brake driver will

not turn off until the vehicle reaches rest.

3 — PROGRAMMABLE PARAMETERS: Output Driver Parameters