beautypg.com

Campbell Scientific AM25T 25-Channel Solid State Multiplexer User Manual

Page 29

background image

Appendix A. Single-Ended Measurements

Example A-4. Measuring Single Ended Thermocouples with the Input Location Indexed and
no Step Loop Index

01: Beginning of Loop (P87)
1: 0 Delay
2: 6Loop

Count


02: Thermocouple Temp (SE) (P13)
1: 2

Reps

2: 21

2.5 mV 60 Hz Rejection Range

3: 1

SE

Channel

4: 1

Type

T

(Copper-Constantan)

5: 1

Ref Temp (Deg. C) Loc [ RefTemp ]

6: 18--

Loc [ TC_1 ]

7: 1.0

Mult

8: 0.0

Offset


03: End (P95)

Example A-5. Measuring Single Ended Thermocouples with the Input Location Indexed and
Step Loop Index

01: Beginning of Loop (P87)
1: 0

Delay

2: 6

Loop

Count


02: Step Loop Index (P90)
1: 2

Step


03: Thermocouple Temp (SE) (P13)
1: 2

Reps

2: 21

2.5 mV 60 Hz Rejection Range

3: 1

SE

Channel

4: 1

Type

T

(Copper-Constantan)

5: 1

Ref Temp (Deg. C) Loc [ RefTemp ]

6: 18--

Loc [ TC_1 ]

7: 1.0

Mult

8: 0.0

Offset


04: End (P95)