Mult, Offset: The Mult and Offset parameters are each a constant, variable,
array, or expression by which to scale the results of the measurement. With a
multiplier (mult) of 1 and an offset of 0, the output is in degrees Celsius.

The AM25T instruction must NOT be placed in a conditional
statement when running in pipeline mode.

NOTE

6.1.1 Example CRBasic Programs

Both CRBasic example programs are written for CR1000 dataloggers. Other
CRBasic dataloggers are programmed similarly.

6.1.1.1 CR1000 Example Program 1

In this example, 25 type T thermocouples are connected to the AM25T. One
AM25T instruction will measure the AM25T’s PRT and the thermocouples.
Table 6-1 shows the wiring used with the example.

TABLE 6-1. Wiring for CR1000 Example 1

Function AM25T

CR1000

+12V Power

12 V

12 V

Power and Shield Ground

Gnd

Gnd

Clock CLK

C5

Reset RES

C4

RTD Excitation

EX

EX1

Common High

HI

1H

Common Low

LO

1L

Example 1. CR1000 Program Using One Instruction to Measure Both the Reference
Temperature and Thermocouples

‘Declare Public Variables
Public Tref
Public TC (25)

‘Define Data Tables
DataTable (Dat15sec,1,-1)
DataInterval

(0,15,Sec,10)

Sample

(1,Tref,IEEE4)

Sample

(25,TC(1),IEEE4)

EndTable

DataTable (Dat5min,1,-1)
DataInterval

(0,5,Min,10)

Average

(1,Tref,IEEE4,False)

Average

(25,TC(1),IEEE4,False)

EndTable

11