1 example cr10(x) programs – Campbell Scientific AM25T 25-Channel Solid State Multiplexer User Manual
Page 18

AM25T Solid State Multiplexer
TABLE 6-3. RTD Excitation Voltage and Measurement Range for AM25T
Multiplexers Prior to Serial Number 1839
Datalogger
Temperature Range
Excitation voltage
Vs Range
Vx Range
21X
-40 to 85°C
-24 to 65°C
250 mV
350 mV
± 5 mV
± 5 mV
± 500 mV
± 500 mV
CR10(X)
-40 to 85°C
-11 to 52°C
350 mV
250 mV
± 7.5 mV
± 2.5 mV
± 2500 mV
± 250 mV
CR7
-40 to 85°C
350 mV
± 15 mV
± 500 mV
6.2.1 Example CR10(X) Programs
The two example CR10(X) programs in this section cover measuring
thermocouples and low level voltage sensors with the differential measurement
instruction. The 21X and CR7 are programmed similarly.
Input locations within the measurement loops must be indexed (--), see
Instruction 87 in the datalogger manual. To index a location, using Edlog ver
6.0 or greater, move the cursor to the Input location label and press “F4”. To
index a location with the datalogger keyboard, press the “C” key when
entering the location number and before the “A” key is pressed.
TABLE 6-4. Wiring for CR10(X) Examples
Function AM25T
CR10(X)
+12V Power
12 V
12 V
Power and Shield Ground
G
Clock CLK
C1
Reset RES
C2
RTD Excitation
EX
E1
Analog Ground
AG
AG
Common High
HI
1H
Common Low
LO
1L
Example 3. CR10(X) Program for Measuring 25 Type T Thermocouples or Voltage Sensors
Using a Differential Instruction
*Table 1 Program
01: 10
Execution
Interval
(seconds)
01: Set Port(s) (P20)
;Configure Control Ports for 1 millisecond pulse
1: 9999
C8..C5
=
nc/nc/nc/nc
2: 9933
C4..C1
=
nc/nc/1ms/1ms
02: Do (P86)
;Turn On AM25T
1: 42
Set Port 2 High
14