2 example cr23x program – Campbell Scientific AM25T 25-Channel Solid State Multiplexer User Manual

Page 22

background image

AM25T Solid State Multiplexer

6.2.2 Example CR23X Program

The CR23X uses Instruction 134 for measuring thermocouples or voltages
with the AM25T. Example 5 is a portion of a datalogger program that uses the
instruction to measure 25 type T thermocouples. Instruction 134 automatically
compensates for long lead lengths.

TABLE 6-5. Wiring for CR23X Example

Function AM25T

CR23X

+12V Power

12 V

12 V

Power and Shield Ground

G

Clock CLK

C1

Reset RES

C2

RTD Excitation

EX

E1

Analog Ground

AG

Common High

HI

1H

Common Low

LO

1L

Example 5. CR23X Program for Measuring 25 Type T Thermocouples

;{CR23X}
;
*Table 1 Program
01: 1

Execution

Interval

(seconds)


01: AM25TMultiplexer (P134)
1: 25

Reps

2: 21

10 mV, 60 Hz Reject, Slow Range

3: 1

AM25T

Channel

4: 1

DIFF

Channel

5: 21

Exchan 1, 60 Hz Reject

6: 1

Clock

Control

7: 2

Reset

Control

8: 1

Type

T

(Copper-Constantan)

9: 1

Ref Temp (Deg. C) Loc [ RefTemp ]

10: 2

Loc [ TC_1 ]

11: 1.0

Mult

12: 0.0

Offset

18