4. WIRING

Power supply requirements, 12-36Vdc, note installation
recommendations as follows:
Terminal Strip:

SMKDSP1.5/2-5.08 Phoenix contact

A. Cable Requirements
• Two core shielded cable
• Cable outer diameter: 0.35˝ to 0.47˝ (9-12mm)

Required for proper installation with cable gland option

• Wire Gauge: 14-22 AWG (multi-strand or solid)

B. Wiring Instructions
• Do not run pressure transmitter cable / wires within the same conduit as high

voltage (line power) line to reduce the potential for noise (interference).
Use dedicated conduit on GC52 cables / wires for optimum results.

• Cable diameter, specified above, must be maintained when using the Cable

Gland termination to retain environmental ratings.

• When connecting shield / drain wire, only connect one end which should be at

the received ground.

• Wire stripping instructions; remove cable jacket 2-3˝ and strip wires 0.25˝.

Shield / drain wire should not be exposed at the pressure transmitter termination.

Terminal box

Display (board)

Shield

Power source

Receiver

Transmission cable

CASE

DISPLAY

CAP

Inside sensor Line

LCD holder

Notch

Transmission cable
(Twist)

Sheath