2.2 Specifications
SP170-PDA W/UPS MODULE
ELECTRICAL
Input
Voltage 120VAC
+12%(135VAC),
-
25%(90VAC)
(before battery use)
Frequency
48 to 62Hz
Current (1250, 1250(PLUS),
2000)
8.8A, 8.8A, 14.3A
Power Factor Corrected
Output
Voltage
120VAC
± 3%
Frequency
50Hz / 60Hz (software select)
Line Sync (software select)
Rating:
SP170-PDA/1250
1250 VA/875 Watts, 10.4A
SP170-PDA/1250(PLUS)
1250 VA/875Watts or 1400 watts
for 10 seconds, 10.4A
SP170-PDA/2000
2000 VA/1400Watts, 16.7A
Total Harmonic Distortion (THD)
3% Typ; 5% Max.
(@100% Non-linear load)
Dynamic Response
±4% for 100% Step Load Change,
0.5 Millisecond Recovery Time
Overload
110% for 10 Minutes;
200% for 50 milliseconds
UPS Protection
Input and Output Short Circuit;
Input and Output Overload;
Excessive Battery Discharge
Output DC
Voltage
24.0 VDC, +3%
Current
0 – 5.0 amps
ENVIRONMENTAL
Operating Temperature
-40
o
C to +74
o
C (-40
o
F to +165
o
F)
Humidity
0% to 95% Non-condensing
Altitude
Sea Level to 10,000 Feet
(some derating of temp.
w/altitude > 6000 ft)
MECHANICAL
Input
Hardwired to Input Terminal
Outputs
Hardwired to Output Terminal
Dimensions (H x W x D) in.
7.0 x 19.0 x 16.0
Weight (lbs)
30
DESIGN
Standard Features
Power Factor Corrected Input;
Fully Regenerative;
True On-Line Continuous Power;
Low Distortion Sinewave Ouput;
Designed for Non-linear Loads;
Extended Brownout Protection;
EIA/RS232 Data Interface;
Specifications
Meets FCC Class A, IEEE
587/ANSI C62.41, IEC 555 @
120 VAC and NEMA Stds.
MTBF
Inverter: > 100,000 hrs.
System w/Bypass: 150,000 hrs
Calculated from Component Spec.
Typical Recharge Time to
85% Capacity at 100% Load
48-72 hrs (more time required with
extended battery option)
Less than 20 hrs with optional Fast
Battery Charger.
CONTROLS AND INDICATORS
LCD Display
System Set-up and System Status
Features including Day and Date,
System Load Level, Battery System
Status and Event Logs.
Controls
Power On; Cold Start; Test; Alarm
Silence; LCD Controls
Audible Alarms
Utility Interrupt; Inverter Failure;
Overload; Low Battery; Self Test
Serial Interface for EIA 232.
Optional NTCIP and TCP/IP via
Standard RJ45 Connector
Full Interactive, Remote Computer
Monitoring and Control of UPS
Functions.
Compatible with Systems Enhancement
UPS Monitor & Control Software
Open-Collector (DB-9F)
Open Collector for Remote
Annunciation of Power Up, Power
Down, On Battery and Low Battery.
Relay Contacts
Normally Open/Normally Closed
4 sets available; can be configured for
various settings; On Batt, Timer,
Battery Capacity, Alarms etc..
Specifications subject to change without notice.