0 troubleshooting table – ARI Armaturen ARI-PREMIO User Manual
Page 52
Page 52
0040501000 4511
Operating and installation instructions
Thrust actuator ARI-PREMIO
9.0 Troubleshooting table
ATTENTION !
- read point 10.0 and 11.0 prior to dismantling and repair work!
- read point 6.0 before restarting the plant !
Fault
Possible Causes
Remedy
Thrust actuator fails to move
Power failure
Ascertain and eliminate cause
Fuse has blown
Replace fuse
Thrust actuator not properly
connected
Rectify connection on thrust
actuator in accordance with wiring
diagram
Short circuit due to:
- moisture
Ascertain exact cause,
- Dry the thrust actuator and
eliminate leakage
- wrong connection
- Rectify connection on thrust
actuator in accordance with
wiring diagram
- motor has burned out
- Check whether the mains voltage
agrees with the voltage specified
on the rating plate. Have motor
changed.
Connector contacts not plugged in/
not properly plugged into jack strip
Insert connector firmly in jack strip
thus affected
(Only for 12 - 15 kN)
Handwheel is still engaged and
does not disengage when the
motor starts up
Unscrew the motor mounting
screw closest to the cable feed-
through. (Manual release of the
handwheel disengagement
mechanism.)
Thrust actuator alternates
between clockwise and
counter-clockwise rotation
Motor operating capacitor
defective
Have motor operating capacitor
replaced
Thrust actuator fails to run to
final positions and also
produces chatter
Load-dependent travel switches
out of
/ defective
Remove thrust actuator and send
to factory for repair
Voltage drop due to excessively
long connecting cables or
inadequate conductor cross-
section
Lay connecting cables in
accordance with requisite output
Mains fluctuations beyond
permissible tolerance travels
Arrange for "clean" mains system
within requisite tolerances
System pressure too high
Reduce system pressure
Periodic failure on thrust
actuator
Loose connection on feedline
Tighten connections on terminal
strips
Thrust actuator is switched off
in retracting direction prior to
load-dependent switch (three-
way valve)
Travel switch S3 not set
corresponding to use
Set travel switch S3 in accordance
with operating instructions