Red Lion ITMA User Manual
Description, Safety summary, Specifications
1
z
USER PROGRAMMABLE INPUT
(THERMOCOUPLE TYPES J, K, T, & E, OR MILLIVOLT)
z
12 TO 42 VDC LOOP POWERED (4 TO 20 MA OUTPUT)
z
MICROPROCESSOR CONTROLLED
z
SIMPLE ADJUSTABLE RANGE SETTING (USING INPUT SIGNAL)
z
THERMOCOUPLE BREAK DETECTION
z
MOUNTS ON “T” AND “G” STYLE DIN RAILS
z
2-WAY ELECTRICAL ISOLATION (INPUT/OUTPUT & POWER)
z
HIGH-DENSITY PACKAGING (22.5 MM WIDE)
z
WIDE OPERATING TEMPERATURE RANGE
DESCRIPTION
The ITMA accepts a thermocouple or millivolt input and converts it into a 4
to 20 mA current output. The 4 to 20 mA output is linearly proportional to the
temperature or the millivolt input. This output is ideal for interfacing to
indicators, chart recorders, controllers, or other instrumentation equipment.
The ITMA is loop-powered which means that the same two wires are
carrying both the power and the output signal. The unit controls the output
current draw from 4 to 20 mA in direct proportion to the input change while
consuming less than 4 mA for power. The conversion to a current output signal
makes the ITMA less susceptible to noise interference and allows accurate
transmission over long distances. The 2-Way isolation allows the use of
grounded thermocouples which can provide additional noise reduction benefits.
The ITMA uses a ten position DIP switch to accomplish the input sensor
configuration, range selection, and unit calibration. A simple range setting
technique (Field Calibration) is used so the actual input signal adjusts the output
current for scaling. This technique eliminates the need for potentiometers which
are vulnerable to changes due to vibration.
The unit is equipped with a universal mounting foot for attachment to
standard DIN style mounting rails, including top hat rail (T) according to EN 50
022 - 35
×
7.5 and 35
×
15, and G profile according to EN 50 035 - G 32.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
SPECIFICATIONS
1. POWER: 12 to 42 VDC *(Loop powered). The power supply must have a
30 mA min. capacity.
[* Min. voltage must be increased to include the drop across any current
display indicator]
2. INPUT: J, K, T, E, mV [selectable via DIP switch]
3. OUTPUT: Loop powered (passive), 4 to 20 mA Linear output
Ripple: Less than 15 mV peak-to-peak max., across 250
Ω
load resistor (up
to 120 Hz frequencies).
4. RANGE & ACCURACY: (12 Bit resolution)
Accuracy: ± ( 0.075% Range + 0.25°C [Conformity] + 0.50°C [Ice Point])
at 23°C after 20 min. warm-up, conforming to ITS-90.
Note: TC Conformity and Ice Point do not apply to mV input.
Relative Humidity: Less than 85% RH (non-condensing)
Span: The input span can be set to a min. of 1/8 of the full scale range,
anywhere within that range.
Thermocouple Accuracy for each type and the corresponding ranges:
MODEL ITMA - INTELLIGENT THERMOCOUPLE MODULE WITH ANALOG OUTPUT
M2068B
POWER/
OUTPUT
+
-
TC
+
-
1
2
3
4
5
6
TEST
ICE POIN
T
3.11 (79.0)
(83.8)
3.30
.886
(22.5)
RED LION CONTROL
S
SWITCH
4
YORK, PA
.M
ADE IN U.S.A
.
OUTPUT CAL
FIELD CA
L
BASIC CA
L
ICE PT EN/DI
S
OPEN SEN DN/U
P
TC TYPE
TC TYPE
TC TYPE
RANG
E
RANG
E
DIP SWITCH SETTINGS
:
MODEL ITM
A
RANG
E
MV
UP
ENABLED DISABLED
OPEN SE
N
DOWN
TC TYPE
E
J
T
K
8
67
1
0
5
1
0
11
0
0
0
0
00
10
01
9
11
1
10
1
0
3
2
0
0
1
0
1
1
0
1
ON =
1
4
2
1
3
10
8
6
5
7
9
ON
OFF =
0
M2069A
ITMA
DIMENSIONS In inches (mm)
TC
(INPUT)
RANGE
ACCURACY
RANGE
WIRE COLOR
BS1843
ANSI
0
-9 to 6 mV
±
0.0113 mV
1
1 1 1 0 1
-9 to 22 mV ± 0.0233 mV
2
1 1 1 1 0
-9 to 63 mV ± 0.0540 mV
mV
3
1 1 1 1 1
-9 to 77 mV ± 0.0645 mV
N/A
N/A
0
0 0 0 0 0 -136 to 111°C
±
0.19°C
1
0 0 0 0 1 69 to 575°C
±
0.38°C
2
0 0 0 1 0
J
338 to 800°C
±
0.35°C
3
0 0 0 1 1 -149 to 862°C
±
0.76°C
Yellow (+)
Blue (-)
White (+)
Red (-)
0
0 0 1 0 0 -200 to 541°C
±
0.56°C
1
0 0 1 0 1 427 to 1132°C
±
0.53°C
2
0 0 1 1 0 648 to 1372°C
±
0.54°C
K
3
0 0 1 1 1 -192 to 1372°C ± 1.17°C
Brown (+)
Blue (-)
Yellow (+)
Red (-)
0
0 1 0 0 0 -225 to 149°C
±
0.28°C
1
0 1 0 0 1 74 to 326°C
±
0.19°C
2
0 1 0 1 0 68 to 400°C
±
0.25°C
T
3
0 1 0 1 1 -200 to 400°C
±
0.45°C
White (+)
Blue (-)
Blue (+)
Red (-)
0
0 1 1 0 0 -111 to 311°C
±
0.32°C
1
0 1 1 0 1 276 to 609°C
±
0.25°C
2
0 1 1 1 0
DIP SWITCH
TYPE RANGE
6 7 8 9 10
377 to 1000°C
±
0.47°C
E
3
0 1 1 1 1
TEMPERATURE
& mV RANGE
-114 to 1000°C ± 0.84°C
Brown (+)
Blue (-)
Violet (+)
Red (-)
1 1 1 0 0
Ice Point
Total Error
( ±0.19°C +
±0.25°C
+ ±0.50°C ) =
±0.94°C
Accuracy Example:
Type “J” Range “0”
-136°C to 111°C
CAUTION: Read complete Instructions prior
to installation and operation of the unit.
Note: DIP switch settings
ON = 1 OFF = 0
Conformity
MODEL NO.
DESCRIPTION
PART NUMBER
ITMA
Intelligent Thermocouple Module
ITMA2003
ORDERING INFORMATION
Range
Bulletin No. ITMA-E
Drawing No. LP0382
Released 04/13
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net