beautypg.com

Red Lion IAMA User Manual

Model iama - universal signal conditioning module, General description, Safety summary

background image

1

3-WAY ISOLATION OF ANALOG SIGNALS

UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS

SELECTED VIA DIP SWITCH SETTINGS

OVER 100 INPUT AND OUTPUT ANALOG CONVERSION

COMBINATIONS

CHOOSE LINEAR OR SQUARE ROOT EXTRACTION MODEL

ALL RANGES ARE FACTORY PRECALIBRATED. CUSTOM FIELD

CALIBRATION IS AVAILABLE FOR ALL RANGES WHILE

MAINTAINING THE FACTORY CALIBRATION FOR FUTURE USE

11 to 36 VDC AND 24 VAC MODULE POWER

GENERAL DESCRIPTION

The IAMA – Universal Signal Conditioning Module Series can isolate and

convert over 100 combinations of analog signal ranges. The IAMA3535

converts and transmits signals linearly proportional to the input, while the

IAMA6262 transmits the scaled square root of the input signal. This allows the

IAMA6262 to provide a signal that is linear to flow rate in applications utilizing

a differential pressure transducer.

DIP switch range selection eliminates the need to order and stock different

modules for each input and output signal range, and allows quick and

convenient setup for over 100 standard signal conversions. By utilizing the

Field mode of calibration, the user can customize the input and output scaling

for odd applications, including reversal of the output relative to the input.

In addition to the conversion capabilities, the IAMA modules feature

optically isolated Input/Output signal circuits and transformer isolated Power to

Input, Power to Output circuits.

The modules’ overall full scale accuracy typically exceed 0.05% depending

upon range selection and scaling. The microprocessor based design provides

ease of field scaling and the onboard E

2

PROM stores scaling values for future

recall. Both models come factory precalibrated for all input and output ranges.

Factory or custom field scaling can be selected by a simple mode switch change.

The IAMA can be factory recalibrated in the field if desired.

The modules’ environmental operating temperature range is -20°C to +65°C.

DIN rail mounting saves time and panel space. The units are equipped with

universal mounting feet for attachment to standard DIN style rails, including top

hat profile rail according to EN50022 - 35x7.5 and 35 x 15 and G profile rail

according to EN50035-G32.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to

prevent damage to either the instrument or equipment connected to it. If

equipment is used in a manner not specified by the manufacturer, the protection

provided by the equipment may be impaired.

ORDERING INFORMATION

MODEL NO. DESCRIPTION

PART NUMBER

IAMA

Linear Universal Signal Conditioning Module

IAMA3535

Square Root Universal Signal Conditioning Module

IAMA6262

SPECIFICATIONS

1. POWER: 11 to 36 VDC, 3 W max. or 24 VAC, ±10%, 50/60 Hz, 4.8 VA max.

2. INPUT/OUTPUT RANGES: See Tables 2 and 3

3. ZERO/SPAN ADJUSTMENTS: Digital (DIP Switch Transition)

4. MAX INPUT SIGNAL:

Current Input: 110 mA DC, 1.1 VDC

Voltage Inputs: Terminal 7- 1 VDC +10%

Terminal 8- 10 VDC +10%

Terminal 9- 100 VDC +10%

5. INPUT RESISTANCE:

Current: 10 Ω

Voltage: > 100 K

6. INPUT PROTECTION: Surge suppressor diodes

7. OUTPUT: Self-powered (Active)

8. MAX OUTPUT CURRENT:

Current Output: 22 mA

Voltage Output: 10 mA

9. LOAD RESISTANCE:

Current Output: ≤ 600 Ω

Voltage Output: ≥ 1 KΩ

10. OUTPUT COMPLIANCE:

Current: 4 to 20 mA, 0 to 20 mA: 12 V min (≤ 600 Ω)

0 to 1 mA: 10 V min (≤10 KΩ)

Voltage: 10 VDC across a min. 1 KΩ load (10 mA). Factory calibrated for

loads of > 1 MΩ.

11. ISOLATION LEVEL INPUT TO OUTPUT: 1.5 kV @ 50/60 Hz, 1 min

12. STEP RESPONSE: To within 99% of full scale: 300 msec

4.20 RE

F

1.08

3.12

(27.5)

(106.7)

(79.2)

10

9

8

7

5

4

3

OFF =

0

DIP SWITCH SETTINGS:

2

1

ON =

1

MC2279X

ON

0

11

0

0-1V

0

0-100m

A

0-50mA 0-20mA 4-20mA 0-10mA 0-5m

A

0-2m

A

0-1m

A

0-10

V

0-100V 0-50

V

0-20

V

0-5V 1-5V 0-2V

0

0 0

0

0 0 0 0

1 1 1 1

1

1

0

1

0 0

0 1 1 1

1 0 0 0

0

1

1

1

1 1

0 1 0 1 0 1 0 1

0

0 0

0

01

1 1 1

0 0 0

1

1

0

1

0

1 0 0

0 0 0

0

1

1

1

1

1

0 1 0

0 1 0

0-50mV

0-100m

V

0-200m

V

0-500m

V

0-20mV

0-20mA 4-20mA

INPU

T

0-5V

0-10

V

0-1m

A

OUTPU

T

0

0

1

0 0

9

0

0

00

0 0

0

0

0 0

1 0 0

1 1

7

0

6

0

8

0

1

0

0 1

10

0

5

0

0

SWITCH

1

0

0

0

0

0

1

1

0

1

1

34

INPUT RANG

E

OUT FIELD/FACT.

IN FIELD/FACT.

OUTPUT RANG

E

10

IIN

1V

OUT+ I

OUT- I

11

12

8

79

INPU

T

COMM

10

V

100V

VDC+

5

46

VDC-

2

13

OUT+

OUT-

V

V

20mA/1mA OUTPU

T

11-36VDC

STATU

S

6

*

*

T

S

U

MC2290C

S

A

T

MADE IN U.S.A

.

RED LION CONTROLS

MODEL IAMA

YORK, PA

.

IAMA

MODEL IAMA - UNIVERSAL SIGNAL CONDITIONING MODULE

DIMENSIONS In inches (mm)

CAUTION: Risk of Danger.

Read complete instructions prior

to installation and operation of the unit.

CAUTION: Risk of electric shock.

Bulletin No. IAMA-J
Drawing No. LP0413
Released 12/13

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

UL Recognized Component,

File # E179259