SPECIFICATIONS (Cont’d)
12. MAIN CONTROL OUTPUT (Heating or Cooling):
Control: PID or ON/OFF.
Output: Time proportioning or linear DC.
Hardware: Plug-in, replaceable output modules.
Cycle time: Programmable.
Auto-tune: When performed, sets proportional band, integral time, and
derivative time values.
Probe Break Action: Programmable.
13. COOLING OUTPUT (Optional):
Control: PID or ON/OFF.
Output: Time proportioning or linear DC
Hardware: Plug-in, replaceable output modules.
Cycle time: Programmable.
Proportional Gain Adjust: Programmable.
Heat/Cool DeadBand: Programmable.
14. LINEAR DC DRIVE (Optional): With digital scale and offset,
programmable deadband and update time.
4 to 20 mA:
Resolution: 1 part in 3500 typ.
Accuracy: ±(0.1% of reading + 25 µA).
Compliance: 10 V (500 Ω max. loop impedance).
0 to 10 VDC:
Resolution: 1 part in 3500 typ.
Accuracy: ±(0.1% of reading + 35 mV).
Min. Load Resistance: 10 KΩ (1 mA max.)
Source: % output power, setpoint, deviation, or temperature.
(Available for heat or cool, but not both.)
15. ALARMS (Optional):
Hardware: Plug-in, replaceable output module.
Modes: Absolute high acting
Absolute low acting
Deviation high acting
Deviation low acting
Inside band acting
Outside band acting
Timed event output(s)
Reset Action: Programmable; automatic or latched.
Delay: Programmable; enable or disable.
Hysteresis: Programmable.
Probe Break Action: Upscale.
Annunciator: LED backlight for “AL1”, “AL2”, (Alarm #2 not available
with cooling output).
16. SERIAL COMMUNICATIONS (Optional):
Type: RS485 Multi-point, Balanced Interface.
Communication Format:
Baud Rate: Programmable from 300-9600.
Parity: Programmable for odd, even, or no parity.
Frame: 1 start bit, 7 data bits, 1 or no parity bit, 1 stop bit.
Unit Address: Programmable from 0-99, max. of 32 units per line.
Transmit Delay: 100 msec min., 200 msec max.
RS485 Common: Isolated from signal input common.
Auto Print Time: Off to 9999 seconds between print-outs.
17. USER INPUT: V
IN
max = 5.25 VDC, V
IL
= 0.85 V
MAX
; V
IH
= 2.0 V
MIN
,
Response time 100 msec max.
Functions:
Program Lock
Print Request
Integral Action Lock
Load Control Point
Auto/Manual Transfer
Run/Hold Profile 1
Setpoint Ramp Select
Run/Stop Profile 1
Reset Alarms
18. ENVIRONMENTAL CONDITIONS:
Operating Temperature: 0 to 50°C
Storage Temperature: -40 to 80°C
Vibration to IEC 68-2-6: Operational 5-150 Hz, 1 g
Shock to IEC 68-2-27: Operational 5 g
Operating and Storage Humidity: 85% max. (non-condensing) from 0°C
to 50°C.
Span Drift: ≤ 100 ppm/°C
Zero Drift: ≤ 1 µ V/°C
Altitude: Up to 2000 meters
19. CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
EN 61010-1
RoHS Compliant
UL Recognized Component: File #E156876
UL Listed: File #E137808
Type 2 Enclosure rating (Face only) for TSC0
Type 4X/IP65 Enclosure rating (Face only) for TSC1
Refer to EMC Installation Guidelines section of the manual for additional
information.
20. CONNECTION: Jaw-type terminal block.
21. CONSTRUCTION:
Front Panel: Flame and scratch resistant tinted plastic.
Case: High impact black plastic. (Mounting collar included).
Type 4X/IP65 model only: Sealed bezel utilizing 2 captive mounting screws
(panel gasket included).This unit is rated for Type 4X/IP65 indoor use.
Installation Category II, Pollution Degree 2.
22. WEIGHT: 1.3 lbs. (0.6 kgs)
BASIC OPERATION
The TSC controls the temperature profile of a system by measuring the
temperature via an input probe, compares the actual temperature to the setpoint
profile in progress, and calculates the new output power value by use of a
modified PID control algorithm. The unit controls the system with the new
output power value so the process temperature conforms to the programmed
profile. The PID control algorithm incorporates features which provide
minimum overshoot and excellent temperature control accuracy for a process.
FRONT PANEL FEATURES
In the normal display mode, the unit will display the process temperature in
the upper display. One of five other parameters may be selected for viewing in
the lower display:
Target Setpoint Profile Phase Time Remaining
% Output Power Temperature Symbol (F/C)
Profile Status
The program profile status display indicates the active profile number with
the current ramp or hold phase of the profile. The profile can be started, stopped,
advanced, etc. from the front panel when the profile status display is viewed, if
not locked from access.
The phase time remaining display, shows the time remaining in a ramp or
hold phase and, if not locked from access, may be changed on-line to effect
temporary changes to the program. Additionally, the target setpoint and %
output power (manual mode only) may also be changed on-line or locked from
operator access.
From the normal operating mode, parameters are selected by use of the PAR
button and modified by use of the UP and DOWN buttons. Parameters are then
entered by the PAR button, which advances the user to the next parameter.
Pressing the DSP button immediately returns the controller to the normal
operating mode from any parameter module. The controller configuration and
parameter settings are stored in an internal E
2