DESCRIPTION (Cont’d)

other process conditions. A control point may have its PID gain set values

disabled when implementing the control point.

The optional RS485 multidrop serial communications interface provides the

capability of two-way communication between a TSC unit and other compatible

equipment such as a printer, a programmable controller, or a host computer. In

multipoint applications the address number of each unit on the line can be

programmed from 0-99. Up to thirty-two units can be installed on a single pair

of wires. The Setpoint value, % Output Power, Setpoint Ramp Rate, etc. can be

interrogated or changed by sending the proper command code via serial

communications. Alarm output(s) may also be reset via the serial communications

interface option.

Optional alarm output(s) may be configured to operate as a timed event

output or as a standard alarm output. As an alarm output it may be configured to

activate according to a variety of actions (Absolute HI or LO, Deviation HI or

LO, or Band IN or OUT) with adjustable hysteresis. Also, a standby feature

suppresses the output(s) on power-up until the temperature stabilizes outside the

alarm region. Timed event output(s) allow the controller to activate other

equipment while a programmed profile is running. Each profile can define up to

16 event states (phases), for each output(s).

An optional secondary output is available for processes that require cooling

which provides increased control accuracy and response.

The optional linear 4 to 20 mA or 0 to 10 VDC output signal is available to

interface with final actuators, chart recorders, indicators, or other controllers. The

output signal can be digitally scaled and selected to transmit one of the following:

% Output Power

Measurement Value

Measurement Value Deviation

Setpoint Value

An optional Type 4X/IP65 rated bezel is available for washdown and/or dirty

environments, when properly installed. Modern surface-mount technology,

extensive testing, plus high immunity to noise interference, makes the controller

extremely reliable in industrial environments.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to

prevent damage to either the instrument or equipment connected to it. If

equipment is used in a manner not specified by the manufacturer, the protection

provided by the equipment may be impaired.

Do not use the TSC to directly command motors, valves, or other actuators

not equipped with safeguards. To do so, can be potentially harmful to persons or

equipment in the event of a fault to the unit. An independent and redundant

temperature limit indicator with alarm outputs is strongly recommended. The

indicators should have input sensors and AC power feeds independent from

other equipment.

SPECIFICATIONS

1. DISPLAY: Dual 4-digit

Upper Temperature Display: 0.4" (10.2 mm) Red LED

Lower Auxiliary Display: 0.3" (7.6 mm) Green LED

Display Messages:

“OLOL” -

Appears when measurement exceeds + sensor range.

“ULUL” -

Appears when measurement exceeds - sensor range.

“OPEN” -

Appears when open sensor is detected.

“SHrt”

-

Appears when shorted sensor is detected (RTD only).

“....”

-

Appears when display value exceeds + display range.

“-...”

-

Appears when display value exceeds - display range.

2. POWER: Switch selectable for 115/230 VAC (+10%, -15%) no observable

line variation effect, 48-62 Hz, 10 VA.

3. ANNUNCIATORS:

6 LED Backlight Status Indicators:

%PW

-

Lower auxiliary display shows power output in (%).

PGM

-

Lower auxiliary display shows profile status or profile

time remaining.

MAN

-

Controller is in manual mode.

OP1

-

Main control output is active.

AL1

-

Alarm #1 is active.

AL2

-

Alarm #2 is active (for Dual Alarm Option)

OP2

-

Cooling output is active (for Cooling Option).

4. CONTROLS: Four front panel push buttons for setup and modification of

controller functions and one external input.

5. SETPOINT PROFILE:

Profiles: 4

Segments Per Profile: 8 ramp/hold segments (linkable to 32 segments).

Ramp Rate: 0.1 to 999.9 degrees/minute or no ramp.

Hold Time: Off or from 0.1 to 999.9 minutes, can be extended to 500 hours

by linking.

Error Band Conformity: Off or from 1 to 9999 degrees deviation, + value

for hold phases, - value for both ramp and hold phases.

Power-On Modes: Stop, auto-start, or profile resume.

Start Mode: Ramps from process temperature.

Program Auto Cycle: 1 to 249, or continuous.

Event Outputs: 2, time activated with profile [uses Alarm output(s)].

Control: Front panel buttons, user input, or RS485 communications.

6. CONTROL POINTS:

Setpoints: 4

PID gain sets: 4

Control: Front panel buttons or user input.

7. SENSOR INPUT:

Sample Period: 100 msec

Response Time: 300 msec (to within 99% of final value w/step input;

typically, response is limited to response time of probe).

Failed Sensor Response:

Main Control Output(s): Programmable preset output.

Display: “OPEN”.

Alarms: Upscale drive.

DC Linear: Programmable preset output.

Normal Mode Rejection: 40 db @ 50/60 Hz (improves with increased

digital filtering).

Common Mode Rejection: 100 db, DC to 50/60 Hz.

Protection: Input overload voltage; 240 VAC @ 30 sec max.

8. THERMOCOUPLE:

Types: T, E, J, K, R, S, B, N or Linear mV.

Input Impedance: 20 MΩ, all types.

Lead Resistance Effect: 20 µV/350 Ω.

Cold Junction Compensation: Less than ±1°C error over 0-50°C ambient

temperature range. Disabled for linear mV type.

Resolution: 1°C/F all types, or 0.1°C/F for T, E, J, K, and N only.

9. RTD: 2, 3 or 4 wire, 100 Ω platinum, alpha = 0.00385 (DIN 43760), alpha =

0.003916

Excitation: 0.175 mA

Resolution: 1 or 0.1 degree

Lead Resistance: 7 Ω max.

10. RANGE AND ACCURACY:

Errors include NIST conformity and A/D conversion errors at 23°C after 20

minutes warm-up. Thermocouple errors include cold junction effect. Errors

are expressed as ±(% of reading) and ±3/4 LSD unless otherwise noted.

TC TYPE

RANGE

ACCURACY

WIRE COLOR

(ANSI)

T

-200 to +400°C

-328 to +752°F

0.20% + 1.5°C

0.20% + 2.7°F

blue

E

-200 to 750°C

-328 to +1382°F

0.20% + 1.5°C

0.20% + 2.7°F

violet

J

-200 to +760°C

-328 to +1400°F

0.15% + 1.5°C

0.15% + 2.7°F

white

K

-200 to +1250°C

-328 to +2282°F

0.20% + 1.5°C

0.20% + 2.7°F

yellow

R

0 to +1768°C

+32 to +3214°F

0.15% + 2.5°C

0.15% + 4.5°F

black

S

0 to +1768°C

+32 to +3214°F

0.15% + 2.5°C

0.15% + 4.5°F

black

B

+200 to +1820°C

+300 to +3300°F

0.15% + 2.5°C

0.15% + 4.5°F

grey

N

-200 to +1300°C

-328 to +2372°F

0.20% + 1.5°C

0.20% + 2.5°F

orange

mV

-5.00 to 56.00

0.15% + 1 LSD

__

RTD

(385)

-200 to +600°C

-328 to +1100°F

0.10% + 0.5°C

0.10% + 0.9°F

__

RTD

(392)

-200 to +600°C

-328 to +1100°F

0.10% + 0.5°C

0.10% + 0.9°F

__

OHMS

1.0 to 320.0

0.15% + 1 LSD

__

11. OUTPUT MODULES [Optional] (For All Output Channels):

Relay:

Type: Form-C (Form-A with RS485 option)

Rating: 5 Amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 HP @

120 VAC (inductive load).

Life Expectancy: 100,000 cycles at max. rating.(Decreasing load and/or

increasing cycle time, increases life expectancy).

Logic/SSR Drive: Can drive multiple SSR Power Units.

Type: Non-isolated switched DC, 12 VDC typical.

Drive: 45 mA max.

Triac:

Type: Isolated, Zero Crossing Detection.

Ratings:

Voltage: 120/240 VAC

Max Load Current: 1 AMP @ 35°C

0.75 AMP @ 50°C

Min Load Current: 10 mA

Off State Leakage Current: 7 mA max. @ 60 Hz

Operating Frequency: 20 to 500 Hz

Protection: Internal Transient Snubber, Fused.