Description (cont’d), Safety summary, Specifications – Red Lion TCU User Manual

Page 2

background image

DESCRIPTION (Cont’d)

OPTIONS

A linear 4 to 20 mA or 0 to 10 VDC output signal is available to interface

with actuators, chart recorders, indicators, or other controllers. The output signal

can be digitally scaled and selected to transmit one of the following: % output

power, process temperature value, process temperature value deviation or

setpoint value. For Linear DC control applications, the adjustable output

demand dampening, output deadband and output update time parameters

expand the versatility of the TCU with final control devices.

The optional Heater Current Monitor serves as a digital ammeter for heater

current monitoring. Current transformer accessory (CT005001), is required. An

alarm event output can be programmed to signal when the heater or heater

control devices have failed, before damage to process material occurs. The

Heater Break alarm triggers under two conditions:

1) The main output (OP1) is “on” and the heater current is below the heater

current alarm value, indicating an aged or failed heater.

2) Output (OP1) is “off” and the heater current is more than 10% of the alarm

value, indicating a shorted heater control device or other problem.
The optional Motorized Valve Positioner directly controls the position of a

valve by the use of twin outputs (open and close) to control the direction of

motor rotation. The motor position defines the opening position of the valve.

Two control modes are possible: position control, which makes use of the

slidewire feedback signal supplied with the positioner and velocity control, in

which no slidewire feedback signal is used. Parameters are provided to adjust

the operation of the valve. These include:

Valve activity hysteresis

Valve update time

Variable control dampening

Slidewire signal fail action

Adjustable valve position limits.

The valve positioner TCU achieves tight process control, yet minimizes

unnecessary valve activity. An alarm event output or display alarm can be

programmed under loss of slidewire feedback or under valve fail detection.

The optional Second Analog Input (0-20 mA DC) can be configured as a

remote setpoint signal or as a secondary process signal. Configuration of the

second analog input as a remote setpoint signal allows ratio control, master

setpoint/multiple slave operation, and the ability to cascade the TCU with

another controller (external cascade). Configuration of the second input as a

secondary process signal allows operation as a two-process cascade controller

within a single unit (internal cascade). In either control mode, parameters are

provided to scale, configure, communicate and monitor the activity of both

analog inputs. A square law linearizer function can be used to linearize signals

derived from flow transmitters.

The optional RS485 multidrop serial communication interface provides two-

way communication between a TCU unit and other compatible equipment such

as a printer, a programmable controller, or a host computer. In multipoint

applications the address number of each unit on the line can be programmed from

0-99. Up to thirty-two units can be installed on a single pair of wires. The

Setpoint value, % Output Power, Setpoint Ramp Rate, etc. can be interrogated or

changed by sending the proper command code via serial communications. Alarm

output(s) may also be reset via the serial communications interface option.

An optional Type 4X/IP65 rated bezel is available for wash down and/or dirty

environments, when properly installed. Modern surface-mount technology,

extensive testing, plus high immunity to noise interference makes the controller

extremely reliable in industrial environments.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to

prevent damage to either the instrument or equipment connected to it. If

equipment is used in a manner not specified by the manufacturer, the protection

provided by the equipment may be impaired.

Do not use the TCU to directly command motors, valves, or other actuators

not equipped with safeguards. To do so, can be potentially harmful to persons

or equipment in the event of a fault to the unit. An independent and redundant

temperature limit indicator with alarm outputs is strongly recommended. The

indicators should have input sensors and AC power feeds independent from

other equipment.

SPECIFICATIONS

1. DISPLAY: Dual 4-digit

Upper Temperature Display: 0.4" (10.2 mm) high red LED

Lower Auxiliary Display: 0.3" (7.6 mm) high green LED

Display Messages (Model dependent):

“OLOL” - Appears when measurement exceeds + sensor range.

“ULUL” - Appears when measurement exceeds - sensor range.

“OPEN” - Appears when open sensor is detected.

“SHrt”

- Appears when shorted sensor is detected (RTD only)

“....”

- Appears when display values exceed + display range.

“-...”

- Appears when display values exceed - display range.

“SLid”

- Appears when loss of slidewire signal is detected.

“VALV”

- Appears when valve actuator error is detected.

2. POWER: Switch selectable for 115/230 VAC (+10%, -15%) no observable

line variation effect, 48 to 62 Hz, 10 VA

3. ANNUNCIATORS:

LED Backlight Status Indicators (Model dependent):

%PW

- Lower auxiliary display shows power output in (%).

DEV

- Lower auxiliary display shows deviation (error)

from temperature setpoint.

OP1

- Main control output is active.

AL1

- Alarm #1 is active.

AL2

- Alarm #2 is active (for Dual Alarm Option).

OP2

- Cooling output is active (for Cooling Option).

OPN

- Valve positioner OPEN output is active

(for Valve Positioner option).

CLS

- Valve positioner CLOSE output is active

(for Valve Positioner option).

CUR

- Lower auxiliary display shows heater current

(for Heater Current Monitor option).

SEC

- Lower auxiliary display shows second analog input

(For Second Analog Input option).

MAN

- Flashing: Controller is in manual mode.

REM

- ON: controller is in remote setpoint mode

(Second Analog Input option).

- OFF: controller is in local setpoint mode

(Second Analog Input option).

- Flashing: controller is in Manual control mode

(Second Analog Input optional).

4. CONTROLS: Four front panel push buttons for modifying and setup of

controller functions and one external input for parameter lockout or other

functions.

5. MAIN SENSOR INPUT:

Sample Period: 100 msec

Response Time: 300 msec (to within 99% of final value w/step input;

typically, response is limited to response time of probe)

Failed Sensor Response:

Main Control Output(s): Programmable preset output

Display: “OPEN”

Alarms: Upscale drive

DC Linear: Programmable preset output

Normal Mode Rejection: 40 dB @ 50/60 Hz (improves with increased

digital filtering.

Common Mode Rejection: 100 dB, DC to 60 Hz

Protection: Input overload 120 VAC for 30 seconds.

6. THERMOCOUPLE:

Types: T, E, J, K, R, S, B, N, Linear mV

Input Impedance: 20 M Ω all types

Lead resistance effect: 20 µV/350 Ω

Cold junction compensation: Less than ±1°C error over 0 - 50°C ambient

temperature range. Disabled for Linear mV type.

Resolution: 1°C/F all types, or 0.1°C/F for T, E, J, K, and N only.

7. RTD: 2, 3 or 4 wire, 100 Ω platinum, alpha = 0.00385 (DIN 43760),

alpha = 0.003916

Excitation: 0.175 mA

Resolution: 1 or 0.1 degree

Lead Resistance: 7 Ω maximum

8. RANGE AND ACCURACY:

Errors include NIST conformity and A/D conversion errors at 23°C after 20

min. warm-up. Thermocouple errors include cold junction effect. Errors are

expressed as ±percent of reading and ±

3

/

4

LSD unless otherwise noted.

TC TYPE

RANGE

ACCURACY

WIRE COLOR

(ANSI)

T

-200 to +400°C

-328 to +752°F

0.20% + 1.5°C

0.20% + 2.7°F

blue

E

-200 to 750°C

-328 to +1382°F

0.20% + 1.5°C

0.20% + 2.7°F

violet

J

-200 to +760°C

-328 to +1400°F

0.15% + 1.5°C

0.15% + 2.7°F

white

K

-200 to +1250°C

-328 to +2282°F

0.20% + 1.5°C

0.20% + 2.7°F

yellow

R

0 to +1768°C

+32 to +3214°F

0.15% + 2.5°C

0.15% + 4.5°F

black

S

0 to +1768°C

+32 to +3214°F

0.15% + 2.5°C

0.15% + 4.5°F

black

B

+200 to +1820°C

+300 to +3308°F

0.15% + 2.5°C

0.15% + 4.5°F

grey

N

-200 to +1300°C

-328 to +2372°F

0.20% + 1.5°C

0.20% + 2.5°F

orange

mV

-5.00 to 56.00

0.15% + 1 LSD

__

RTD

(385)

-200 to +600°C

-328 to +1100°F

0.10% + 0.5°C

0.10% + 0.9°F

__

RTD

(392)

-160 to +600°C

-256 to +1100°F

0.10% + 0.5°C

0.10% + 0.9°F

__

OHMS

1.0 to 320.0

0.15% + 1 LSD

__

2