Red Lion LDSG User Manual
Page 9
![background image](/manuals/408914/9/background.png)
9
RESET TOTALIZER
When activated (momentary action),
flashes and the Totalizer resets to
zero. The Totalizer then continues to operate as it is configured. This selection
functions independent of the selected display.
RESET AND ENABLE TOTALIZER
When activated (momentary action),
flashes and
the Totalizer resets to zero. The Totalizer continues to
operate while active (maintained action). When the user
input is released, the Totalizer stops and holds its value. This
selection functions independent of the selected display.
ENABLE TOTALIZER
The Totalizer continues to operate as long as activated
(maintained action). When the user input is released, the
Totalizer stops and holds its value. This selection functions
independent of the selected display.
SELECT MAXIMUM DISPLAY
The Maximum display is selected as long as activated
(maintained action). When the user input is released, the
Input Display returns. The
DSP key overrides the active
user input. The Maximum continues to function independent
of being displayed.
RESET MAXIMUM
When activated (momentary action),
flashes and
the Maximum resets to the present Input Display value. The
Maximum function then continues from that value. This
selection functions independent of the selected display.
RESET, SELECT, ENABLE MAXIMUM DISPLAY
When activated (momentary action), the Maximum value
is set to the present Input Display value. Maximum continues
from that value while active (maintained action). When the
user input is released, Maximum detection stops and holds its
SELECT MINIMUM DISPLAY
The Minimum display is selected as long as activated
(maintained action). When the user input is released, the
Input Display is returned. The
DSP key overrides the active
user input. The Minimum continues to function independent
of being displayed.
RESET MINIMUM
When activated (momentary action),
flashes and
the Minimum reading is set to the present Input Display
value. The Minimum function then continues from that value.
This selection functions independent of the selected display.
value. This selection functions independent of the selected display. The
DSP key
overrides the active user input display but not the Maximum function.
RESET, SELECT, ENABLE MINIMUM DISPLAY
When activated (momentary action), the Minimum value
is set to the present Input Display value. Minimum continues
from that value while active (maintained action). When the
user input is released, Minimum detection stops and holds
RESET MAXIMUM AND MINIMUM
When activated (momentary action),
flashes and the Maximum and
Minimum readings are set to the present Input Display value. The Maximum and
Minimum function then continues from that value. This selection functions
independent of the selected display.
CHANGE DISPLAY INTENSITY LEVEL
When activated (momentary action), the display intensity changes to the next
intensity level (of 4). The four levels correspond to Display Intensity Level
(
) settings of 0, 3, 8, and 15. The intensity level, when changed via the
User Input/ Function Key, is not retained at power-down, unless Quick
Programming or Full Programming mode is entered and exited. The meter will
power-up at the last saved intensity level.
its value. This selection functions independent of the selected display. The
DSP
key overrides the active user input display but not the Minimum function.
SETPOINT SELECTIONS
The following selections can be programmed for user inputs or front panel
function keys. Refer to Module 6 for an explanation of their operation.
-
Select main or alternate setpoints
-
Reset Setpoint 1 (Alarm 1)
-
Reset Setpoint 2 (Alarm 2)
-
Reset Setpoint All (Alarm All)
PRINT REQUEST
The meter issues a block print through the serial port when activated. The
data transmitted during a print request is programmed in Module 7. If the user
input is still active after the transmission is complete (about 100 msec), an
additional transmission occurs. As long as the user input is held active,
continuous transmissions occur.