List of factory default settings – Vaisala vNet PoE Network Interface User Manual
Page 34

28
VAISALA
To manually restore factory default settings:
On the vNet Device itself, press and hold the restart button
for at least five (5) seconds (see Figure 3, “Restart button on
vNet Device,” on page 30).
Important:
There is no warning before the factory default set-
tings are restored.
List of Factory Default Settings
For an explanation of each setting shown below, refer to Table 1,
“Configuration Backup File” on page 23.
These configuration settings are returned to factory default
settings if the
Keep IP Settings and Administrator Password
option
is checked:
Item
Setting
RealPort
771
RawPort
9761
IdleTimeout
5
CloseTimeout
True
DeviceName
vNet XXXXXXXX, where “X” is the 8-
digit serial number of the vNet Device
Contact
(blank)
Enable15V
Off (if installed)
EnableFan
On (if installed)
viewLinc Aware Enabled
True
viewLinc Aware Lookup
Interval
120 seconds
viewLinc Aware Reinstate
interval
600 seconds
Table 2: Factory Default Settings not including IP Settings and
Administrator Password