Water heater installation – State SBD85 365NE A User Manual

Page 21

background image

21

of the Canadian Electrical Code CSA C22.1 and/or local codes.

Vent installation
Seal all joints between the power venter and the vent

termination. This is to prevent leakage of exhaust products

into the room(s) due to positive pressure of blower.
The “Sequence of Operation” description will be the same with

mechanical venting except;
When the water heater thermostat calls for heat:
Thermostat contacts “Close” and the power venter blower

(120 VAC) is energized. Sufficient draft must be established

for the “Draft Prover Switch (N.O.)” to “Close”. When the

draft prover switch “Closes” the relay coil of the flue damper

is energized.

water heater installation

mechanical Venting

single unit installation
When mechanical venting of these heaters is desired, the

following kits are available.
Models with inputs from 120,000 to 200,000 btu/h

Part number 9005381205
Models with inputs from 250,000 to 390,000 btu/h

Part number 9003434205
Where an approved power venter is to be installed to operate

in conjunction with the water heater thermostat, the following

codes must be adhered to. Field wiring should conform to

the current edition of the National Electrical Code NFPA 70.

For Canadian installations the electrical connections and

grounding shall be done in accordance with the current edition

water piping diagrams
This manual provides detailed water piping diagrams for typical

methods of application for the water heaters, see Water Piping

Diagrams beginning on page 40.
The water heater may be installed by itself, or with a separate

storage tank. When used with a separate storage tank, the

circulation may be either by gravity or by means of circulating

pump. Adjust flow by throttling a full port ball valve installed in the

circulating line on the outlet side of the pump. Never throttle flow

on the suction side of a pump. See the Water Piping Diagrams

beginning on page 40.
note: In addition to the factory installed Temperature-Pressure

Relief Valve (T&P valve) on the water heater, each remote

storage tank that may be installed and piped to a water heating

appliance must also have its own properly sized, rated and

approved Temperature-Pressure Relief Valve installed.
Call the toll free technical support phone number listed on the

back cover of this manual for further assistance in sizing a T&P

valve for remote storage tanks.

t&p ValVe discharge pipe

Explosion Hazard

Temperature-Pressure Relief Valve

must comply with ANSI Z21.22-

CSA 4.4 and ASME code.

Properly sized temperature-

pressure relief valve must be

installed in opening provided.

Can result in overheating and

excessive tank pressure.

Can cause serious injury or death.

water line connections

The water piping installation must conform to these instructions

and to all local code authority having jurisdiction. Good practice

requires that all heavy piping be supported.
Read and observe all requirements in the following sections

before installation of the water piping begins:
1. Water Temperature Control and Mixing Valves on page 13.
2. Dishwashing Machines on page 14.
3. Temperature-Pressure Relief Valve on page 14-15.
4. Closed Systems and Thermal Expansion on page 14.
5. For multiple water heater installations see Water Piping

Diagrams beginning on page 40.

water (potaBle) heating and space heating
1. All piping components connected to this unit for space

heating applications shall be suitable for use with potable

water.

2. Toxic chemicals, such as those used for boiler treatment,

shall NEVER be introduced into this system.

3. This unit may NEVER be connected to any existing heating

system or component(s) previously used with a non-potable

water heating appliance.

4. When the system requires water for space heating at

temperatures higher than required for domestic water

purposes, a tempering valve must be installed. Please

refer to installation diagrams beginning on page 40 of this

manual for suggested piping arrangements.

5. These water heaters cannot be used in space heating

applications only

thermometers (not supplied)
Thermometers should be obtained and field installed as shown

in the installation diagrams.
Thermometers are installed in the system as a means of

detecting the temperature of the outlet water supply.