beautypg.com

Venting installation – State SBD85 365NE A User Manual

Page 16

background image

16

direct Vent appliances
Appliances installed in a Direct Vent configuration that derive all

air for combustion from the outdoor atmosphere through sealed

intake air piping are not factored in the total appliance input Btu/

hr calculations used to determine the size of openings providing

fresh air into confined spaces.
eXhaust fans
Where exhaust fans are installed, additional air shall be provided

to replace the exhausted air. When an exhaust fan is installed

in the same space with a water heater, sufficient openings to

provide fresh air must be provided that accommodate the

requirements for all appliances in the room and the exhaust fan.

Undersized openings will cause air to be drawn into the room

through the water heater’s vent system causing poor combustion.

Sooting, serious damage to the water heater and the risk of fire

or explosion may result. It can also create a risk of asphyxiation.
louVers and grilles
The free areas of the fresh air openings in the instructions that

follow do not take in to account the presence of louvers, grilles or

screens in the openings.
The required size of openings for combustion, ventilation and

dilution air shall be based on the “net free area” of each opening.

Where the free area through a design of louver or grille or screen

is known, it shall be used in calculating the size of opening

required to provide the free area specified. Where the louver and

grille design and free area are not known, it shall be assumed

that wood louvers will have 25% free area and metal louvers and

grilles will have 75% free area. Non motorized louvers and grilles

shall be fixed in the open position.

unconfined space

An Unconfined Space is one whose volume IS NOT LESS THAN

50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the

total input rating of all appliances installed in the space. Rooms

communicating directly with the space, in which the appliances

are installed, through openings not furnished with doors, are

considered a part of the unconfined space.
Makeup air requirements for the operation of exhaust fans,

kitchen ventilation systems, clothes dryers and fireplaces shall

also be considered in determining the adequacy of a space to

provide combustion, ventilation and dilution air.
unusually tight construction
In unconfined spaces in buildings, infiltration may be adequate

to provide air for combustion, ventilation and dilution of flue

gases. However, in buildings of unusually tight construction (for

example, weather stripping, heavily insulated, caulked, vapor

barrier, etc.) additional air must be provided using the methods

described in the Confined Space section that follows.

confined space

A Confined Space is one whose volume is less than 50 cubic

feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input

rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion,

ventilation and dilution in confined spaces. The required size for

the openings is dependent on the method used to provide fresh

air to the confined space and the total Btu/hr input rating of all

appliances installed in the space.

Venting

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST

BE FOLLOWED TO AVOID CHOKED COMBUSTION OR

RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE

SOOTING OR RISKS OF FIRE AND ASPHYXIATION.
Heater must be protected from freezing downdrafts.
Remove all soot or other obstructions from the chimney that will retard

a free draft.
Type B venting is recommended with these heaters. For typical venting

application see TECHNICAL DATA VENTING on pages 19 and 20.
This water heater must be vented in compliance with all local codes,

the current revision of the National Fuel Gas Code (ANSI-Z223.1) and

with the Category I Venting Tables.
If any part of the vent system are exposed to ambient temperatures

below 40°F it must be insulated to prevent condensation.
• Do not connect the heater to a common vent or chimney with solid

fuel burning equipment. This practice is prohibited by many local

building codes as is the practice of venting gas fired equipment to

the duct work of ventilation systems.

• Where a separate vent connection is not available and the vent pipe

from the heater must be connected to a common vent with an oil

burning furnace, the vent pipe should enter the smaller common

vent or chimney at a point above the large vent pipe.

Vent reducer

Model SBD71120(N,P)E is shipped with a 6" to 5" flue outlet

adapter. Models SBD100250(N,P)E(A), SBD65251(N,P)E(A) and

SBD100275(N,P)E(A) are shipped with a 8" to 6" flue outlet adapter.

Each adapter fits on top of the installed flue damper. Use only vent

reducers supplied with the unit. The venting must comply with the

current editions of the NATIONAL FUEL GAS CODE, ANSI Z223.1/

NFPA 54 or NATURAL GAS AND PROPANE INSTALLATION CODE

CAN/CSA-B149.1

figure 11.

figure 12.

Venting installation