beautypg.com

Caution, Installation considerations, Fire or explosion hazard – State SBD85 365NE A User Manual

Page 10

background image

10

Flammable items, pressurized containers or any other potential

fire hazardous articles must never be placed on or adjacent to

the heater. Open containers or flammable material should not be

stored or used in the same room with the heater.

The heater must not be located in an area where it will be subject

to freezing.

Locate it near a floor drain. The heater should be located in an

area where leakage from heater or connections will not result

in damage to adjacent area or to lower floors of the structure.

When such locations cannot be avoided, a suitable metal drain

pan should be installed under heater. Such pans should be

fabricated with sides at least 2” deep, with length and width at

least 2” greater than diameter of heater and must be piped to

an adequate drain. Pan must not restrict combustion air flow.

clearances

These heaters are approved for installation on combustible flooring

in an alcove when the minimum clearance from combustion or

non-combustible construction are followed as indicated in Figure 6

and Table 4.

In all installations the minimum combustible clearances from draft

hood surface or vent piping shall be 6” (152mm). Vent piping passing

through a combustible wall or ceiling must be a continuous run

(no joints) and retain 6” (152mm) clearance unless an approved

reducing thimble is used.

A service clearance of 24” (610mm) should be maintained from

serviceable parts, such as relief valves, baffles, thermostats, cleanout

openings or drain valves.

taBle 4. installation clearances

a

(right side)

B

(leftside)

c

(Back)

d

(ceiling)

sBd71120(n,p)e

1” (2.54 cm) 1” (2.54 cm) 1” (2.54 cm) 12” (30.48 cm)

sBd81154(n,p)e

1” (2.54 cm) 1” (2.54 cm) 1” (2.54 cm) 12” (30.48 cm)

sBd81180(n,p)e

1” (2.54 cm) 1” (2.54 cm) 1” (2.54 cm) 12” (30.48 cm)

sBd100199(n,p)et

1” (2.54 cm) 1” (2. 54 cm) 1” (2.54 cm) 12” (30.48 cm)

sBd100199(n,p)e

1” (2.54 cm) 1” (2. 54 cm) 1” (2.54 cm) 12” (30.48 cm)

sBd81199(n,p)e

1” (2. 54 cm) 1” (2. 54 cm) 1” (2. 54 cm) 12” (30.48 cm)

sBd100199(n,p)es(a)

1” (2. 54 cm) 1” (2. 54 cm) 1” (2. 54 cm) 12” (30.48 cm)

sBd100250(n,p)e(a)

2” (5.08 cm) 2” (5.08 cm) 2” (5.08 cm) 12” (30.48 cm)

sBd65251(n,p)e(a)

2” (5.08 cm) 2” (5.08 cm) 2” (5.08 cm) 12” (30.48 cm)

sBd100275(n,p)e(a)

2” (5.08 cm) 2” (5.08 cm) 2” (5.08 cm) 12” (30.48 cm)

sBd65305(p,n)e(a)

2” (5.08 cm) 2” (5.08 cm) 2” (5.08 cm) 12” (30.48 cm)

sBd85365(n,p)e(a)

3” (7.75 cm) 3” (7.75 cm) 3” (7.75 cm) 12” (30.48 cm)

sBd100390(n,p)e(a)

3” (7.75 cm) 3” (7.75 cm) 3” (7.75 cm) 12” (30.48 cm)

locating the water heater

Property Damage Hazard

All water heaters eventually leak.

Do not install without adequate drainage.

CAUTION

When installing the heater, consideration must be given to proper

location. Location selected should be as close to the stack or chimney

as practicable, with adequate air supply and as centralized with the

piping system as possible.

Fire or Explosion Hazard

Read instruction manual before

installing, using or servicing

water heater.

Avoid all ignition sources if you smell gas.

Do not store or use gasoline or other flammable vapors and

liquids in the vicinity of this or any other appliance.

Use only the gas shown on the water heater rating label.

Keep ignition sources away from faucets after extended

periods of non-use.

Maintain required clearances to combustibles.

Do not expose water heater controls to excessive gas

pressure.

There is a risk in using fuel burning appliances such as gas water

heaters in rooms, garages or other areas where gasoline, other

flammable liquids or engine driven equipment or vehicles are stored,

operated or repaired. Flammable vapors are heavy and travel along

the floor and may be ignited by the heater’s igniter or main burner

flames causing fire or explosion. Some local codes permit operation

of gas appliances in such areas if they are installed 18” or more

above the floor. This may reduce the risk if location in such an area

cannot be avoided.

Do not install this water heater directly on a carpeted floor. A fire

hazard may result. Instead the water heater must be placed on a

metal or wood panel extending beyond the full width and depth by at

least 3 inches in any direction. If the heater is installed in a carpeted

alcove, the entire floor shall be covered by the panel. Also, see the

DRAINING requirements in MAINTENANCE Section.

The heater shall be located or protected so it is not subject to physical

damage by a moving vehicle.

installation considerations