Thermal and air flow performance, Environmental specifications, Hp 642 1200mm rack specifications – HP Modular Cooling System User Manual
Page 61
Specifications 61
Thermal and air flow performance
Maximum thermal and air flow
performance parameters
Single rack
Dual rack
(Specification per rack)
Air temperature—Inlet to rack-mounted
components
25ºC (68ºF)
25ºC (68ºF)
Chilled water temperature
7º–16°C (45º–60°F)
7º–16°C (45º–60°F)
Total rack-mounted component air flow 4,500 cfm (7,650 m3/h) or less at
0 or more pressure drop across the
rack mounted components
2,400 cfm (4,050 m3/h) or less at
0 or more pressure drop across the
rack mounted components
Chilled water flow rate
124 l/min (32.8 US gal/min)
124 l/min (32.8 US gal/min)
Chilled water pressure differential at
flow needed to meet thermal
specifications
1.0 bar delta pressure
1.0 bar delta pressure
Heat lost to room
Approximately 10% maximum
depending on the MCS settings
and room temperature
Approximately 10% maximum
depending on the MCS settings
and room temperature
Server heat load
50 kW maximum
25 kW maximum
Environmental specifications
Features
Specifications
Operating temperature:
Recommended
Allowable
18ºC (64.4ºF) to 27ºC (80.6ºF)
15ºC to 32ºC (59ºF to 90ºF)
Non-operating temperature 0ºC to 60ºC (32ºF to 140ºF)
Transit temperature
-30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours
Storage temperature
-20ºC to 60ºC (-4ºF to 140ºF)
Operating humidity:
Recommended minimum
Recommended maximum
Allowable range
5.5°C (41.9°F) dew point
60% relative humidity and 15°C (59°F) dew point
20 to 80% relative humidity (non-condensing)
Non-operating humidity
5 to 95% relative humidity (non-condensing)
Operating altitude
-76.2 to 3,048 m (-250 to 10,000 ft)
Non-operating altitude
-76.2 to 9,144 m (-250 to 30,000 ft)
NOTE:
For safety, the MCS 5042 unit is equipped with a dew point sensor and control system
which creates an alarm that sounds if the chilled water temperature is lower than the dew point
temperature. This condition might create excessive condensation on the heat exchanger.
Therefore, the unit must be operated in non-condensing operating conditions.
HP 642 1200mm Rack specifications
U height
Width
Depth
Dynamic load (gross)
Static load
42U
598 mm
(23.8 in)
1,300 mm
(47.24 in)
1,043 kg
(2,300 lb)
1,361 kg
(3,000 lb)