Installation 27
1.
Route the water hoses from the HP Hook Up Kit through the floor cut-out, and then use a hose wrench to
install each main hose to the MCS 5042 unit. For information on floor cut out dimensions, see the HP
mc-Series 5042 Rack Site Preparation Guide.
2.
Route the two drain hoses to the drain collection system catch basin:
a.
Install and route the blue drain hose into either the water return line or the gravity drain collection
system catch basin.
b.
Route the preinstalled clear drain hose into the gravity drain collection system catch basin.
c.
Position the gravity drain collection system below the water collection pan, enabling gravity to draw
the water out of the water collection pan and into the gravity drain collection system basin.
3.
Log in to the web interface:
a.
Enter the user name in the User Name field. The default user name is Admin.
b.
Enter the password in the Password field. The default password is Admin.
- Surge Protectors (2 pages)
- EXPANSION BASE 344524-001 (74 pages)
- DESKJET 712C (22 pages)
- 224M (166 pages)
- 6308M-SX (8 pages)
- 2103R-CSDI (92 pages)
- Webcam (3 pages)
- 4100GL (228 pages)
- XP10000 (82 pages)
- 326431 (2 pages)
- 2520G-POE (101 pages)
- 5300 (164 pages)
- Elite Autofocus Webcam (20 pages)
- 5400zl Series (16 pages)
- 2610 (364 pages)
- 8200ZL (314 pages)
- DV6 (130 pages)
- HD-3100 (2 pages)
- 9308M (27 pages)
- 6108 (300 pages)
- 2600 Series (306 pages)
- DC149B (3 pages)
- 2600-PWR (418 pages)
- 3110 (22 pages)
- INTEGRITY RX3600 (356 pages)
- 6400CL (84 pages)
- INSIGHT DYNAMICS T8671-91017 (54 pages)
- 4000M (2 pages)
- 16501A LOGIC (130 pages)
- 445946-001 (198 pages)
- RZ406AA (3 pages)
- DX2300 (35 pages)
- 8000M (304 pages)
- 1700-24 (56 pages)
- zl (86 pages)
- 336044-B21 (9 pages)
- 6600 (450 pages)
- 409054-003 (105 pages)
- 2000fc (23 pages)
- 480-0005-00-15 (185 pages)
- 339820-002 (78 pages)
- 263924-002 (135 pages)
- 372284-001 (48 pages)
- 4400 (31 pages)
- A.06.11 (344 pages)