HP Modular Cooling System User Manual

Page 55

background image

Operator display 55

Indicators

Meaning

Condition

The water level has exceeded the permissible level of the condensation

pump sensor.

Modules or sensors

Condensation pump sensor

SNMP notification

Warning

Type of message

Warning

Solution:

1.

To determine the cause, look for leaks or condensation.

2.

If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Cycles
Warning Threshold field.

IMPORTANT:

Use caution when entering temperatures in the Condensation Pump Threshold

fields. Be sure to determine the proper default settings to prevent false alarms, without masking
problems with the MCS.

Default settings will vary, depending on the humidity level of your data center and the heat load

generated by the equipment in the MCS.

The condensation pump has run more than x seconds

Indicators

Meaning

Operator display alarm
message

Excessive moisture

Web interface alarm

message

The condensation pump has run more than x seconds

Condition

The water level has exceeded the permissible level of the condensation pump sensor.

Modules or sensors

Condensation pump sensor

SNMP notification

Warning

Type of message

Warning

Solution:

1.

To determine the cause, look for leaks or condensation.

2.

If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Running

Time Warning Threshold field.

IMPORTANT:

Use caution when entering temperatures in the Condensation Pump Threshold

fields. Be sure to determine the proper default settings to prevent false alarms, without masking

problems with the MCS.

Default settings will vary, depending on the humidity level of your data center and the heat load

generated by the equipment in the MCS.

NOTE:

A 24-hour clock starts when the condensation pump runs for the first time in more than 24

hours. A warning is issued if either the cycle threshold or pump running time is exceeded within
the 24-hour window. The clock stops and the counters are reset to zero for warning purposes if the

thresholds are not exceeded within 24 hours after the last time the condensation pump runs.