beautypg.com

Attaching outer-rails to the rack – HP Netserver L Server series User Manual

Page 123

background image

Chapter 13

Alternative Rack Mounting (4–Post)

117

1. Find the EIA unit markings on the rack and the location for the Netserver.

The screw holes cover a span of only one EIA unit, which is the height
requirement of the HP Netserver.

NOTE

The Netserver can only be mounted into both holes of one EIA
Unit, but cannot be mounted across two EIA units. You cannot
use a hole in one EIA unit and a hole in another EIA unit.

2. Use the masking tape (or marking pen) to mark above the 3rd hole up on both

front columns, as shown in Figure 13-3.

3rd Hole

From Bottom
1st Hole
From Bottom

Bottom of

HP Netserver

Masking

Tape
Marker

represents

the EIA unit
numbers on the

columns rack

Rear of

Rack

Front of

Rack

Mark this face of

the columns with

masking tape

or marker pen.

Left
Side

Right
Side

Figure 13-3. Location Marks on the Rack's Columns

3. Mark the inside face of the left-rear and right-rear rack columns, with masking

tape, as shown in Figure 13-3.

Attaching Outer-Rails to the Rack

No tools are required to attach the outer-rail assemblies to the rack columns.

1. Pull the anti-tip foot forward out of the bottom of the rack.

See Figure 13-4 for the anti-tip foot location.

2. Lower the leveler screws on the rack's lower four corners to make firm

contact with the floor. See Figure 13-4.

3. Align the left outer-rail assembly to the left front and rear columns as shown

in Figure 13-4.