2 parameter description – TOHO ELECTRONICS TTM-P9 User Manual
Page 13
![background image](/manuals/373630/13/background.png)
12
From reset mode
Hold the
▽ key and the PATT./STEP
key down simultaneously.
Set an alarm output lower limit.
Set an alarm output upper limit.
↓
Press the PATT./STEP key.
PV
SV
PV
SV
・
↓
Press the PATT./STEP key.
⑧ PID setting mode (The SET lamp lights.)
- This mode will set the PID constant (only during operation).
6.2 Parameter description
Program setting mode parameters
Character
Description
Initial value
Setting range
□
Set a step
□ temperature
0
Setting range (K: 0 to 1200
°
C/J: 0 to 800
°
C/R: 0 to 1300
°
C
□
Set a step
□ time
0.00
0 to 99 hours 59 minutes
Common parameter setting mode parameters
Character
Description
Initial value
Setting range
Set the PV correction zero
point
0
-199 to +199°C
Set the PV correction gain 1.00
0.50 to 2.00 times
Forward/reverse
switchover
2
1: Forward action (cooling)/2: reverse action (heating)
Sensor switchover
1
1: K thermocouple/2: J thermocouple/3: R thermocouple
SV limiter upper limit
1200
SLL + 50°C to setting range upper limit
SV limiter lower limit
0
0
°
C to SLH-50
°
C
Set the number of patterns 8
1 to 15 patterns
Select PV/SV start
PV
PV: PV start/SV: SV start
Set an SV start
temperature
0
Lower limit to upper limit of the temperature setting range
Proportional period
R (relay output): 20
S (SSR output): 2
1 to 120 seconds
Wait zone
0
0 to 100
°
C
Wait time
0.00
0 to 99 hours 59 minutes
Time signal/alarm output
type
00
(time signal)
0: Nil (time signal)
1: Deviation upper and lower limit
2: Deviation upper limit
3: Deviation lower limit
4: Deviation upper and lower limit
range
5: Absolute value upper and lower
limit
6: Absolute value upper limit
7: Absolute value lower limit
8: Absolute value upper and lower
limit range
0: No additional functions
1: Output
held
2: Standby
sequence
3: Output held + standby
sequence
Alarm output sensitivity
1
0 to 199°C
Time signal ON time
0.00
0 to 99 hours 59 minutes
Time signal OFF time
0.00
0 to 99 hours 59 minutes
Select an external
operation
OFF
ON: external operation /OFF: internal operation
Lock the key
OFF
ON/OFF