40
Identifier
Relative
address
Absolute
address
Character
Name
R/W
Description
TRP
00A2h
40163
Transfer output
normal/reverse switch setting
R/W R/W the forward/reverse operation
switchover setting for transmission output
TRH
00A4h
40165
Transfer output scaling
high limit setting
R/W R/W the upper limit setting for transmission
output scaling
TRL
00A6h
40167
Transfer output scaling
low limit setting
R/W R/W the lower limit setting for transmission
output scaling
TST
00A8h
40169
Timer start/stop
R/W R/W the timer start/stop
Start: 00001
Stop: 00000
OM1
00AAh
40171
Output status monitor
R
Read the output monitor
①②③④⑤
⑤
: OUT1 (1:ON 0:OFF)
④
: OUT2 (1:ON 0:OFF)
③
: EV1 (1:ON 0:OFF)
②
: EV2 (1:ON 0:OFF)
EM1
00ACh
40173
DI status monitor
R
Read the DI monitor
ON: 00001 OFF: 00000
□AT
00AEh
40175
Start/release AT
R/W R/W the start/release AT
STR
00B0h
40177
Store data
W
Store data
Identifiers used only in blind setting
Identifier
Relative
address
Absolute
address
Character
Name
L/B
Description
000
SET0
L/B
Blinding enabled: 00000
Blinding disabled: 00001
001
SET1
L/B
Blinding enabled: 00000
Blinding disabled: 00001
002
SET2
L/B
Blinding enabled: 00000
Blinding disabled: 00001
003
SET3
L/B
Blinding enabled: 00000
Blinding disabled: 00001
004
SET4
L/B
Blinding enabled: 00000
Blinding disabled: 00001
005
SET5
L/B
Blinding enabled: 00000
Blinding disabled: 00001
006
SET6
L/B
Blinding enabled: 00000
Blinding disabled: 00001
007
SET7
L/B
Blinding enabled: 00000
Blinding disabled: 00001
008
SET8
L/B
Blinding enabled: 00000
Blinding disabled: 00001