Table of identifiers (codes) – TOHO ELECTRONICS TTM000 User Manual
Page 37

37
9. Table of identifiers (codes)
For the setting range, options, initial values, and similar parameters, see the operation manual for
this system.
a) Identifier:
This code represents an item. Enter this code in the identifier field in the
message. The □ in the frame represents an SP (ASCII code: 20H).
b) Character:
The character to be displayed on the system screen.
c) Name:
Item name
d) R/W:
This specifies which is possible: reading, writing, or both.
e) Description:
Note: The R/W to characters that do not meet the display conditions responds with "NAK2."
Example: If no EV2 option is selected, the R/W to the EV2 character becomes "NAK2."
Identifier Relative
address
Absolute
address
Character
Name
R/W
Description
PV1
0000h
40001
Setting value (PV)
R
Use it as monitor for measurements (PV).
When overscale: HHHHH
When underscale: LLLLL
SV1
0002h
40003
Setting value (SV)
R/W R/W the setting value (SV)
PR1
0004h
40005
Setting for 1st Priority display
R/W RW the priority screen function setting 1
Example:
INP (identifier)
PR2
0006h
40007
Setting for 2nd Priority display
R/W RW the priority screen function setting 2
Example: □□INP (identifier)
PR3
0008h
40009
Setting for 3rd Priority display
R/W RW the priority screen function setting 3
Example: □□INP (identifier)
PR4
000Ah
40011
Setting for 4th Priority display
R/W RW the priority screen function setting 4
Example: □□INP (identifier)
PR5
000Ch
40013
Setting for 5th Priority display
R/W RW the priority screen function setting 5
Example: □□INP (identifier)
PR6
000Eh
40015
Setting for 6th Priority display
R/W RW the priority screen function setting 6
Example: □□INP (identifier)
PR7
0010h
40017
Setting for 7th Priority display
R/W RW the priority screen function setting 7
Example: □□INP (identifier)
PR8
0012h
40019
Setting for 8th Priority display
R/W RW the priority screen function setting 8
Example: □□INP (identifier)
PR9
0014h
40021
Setting for 9th Priority display
R/W RW the priority screen function setting 9
Example: □□INP (identifier)
INP
0016h
40023
Input type setting
R/W R/W the input type setting
PVG
0018h
40025
PV correction gain
R/W R/W the PV corrected gain setting
PVS
001Ah
40027
Zero point setting for PV correction
R/W R/W the PV corrected zero point setting
001Ch
40029
Filter input
R/W R/W the input filter setting
□DP
001Eh
40031
Position for decimal point
R/W R/W the decimal position setting
No decimal point: 00000
Decimal point: 00001
□FU
0020h
40033
FUNC key setting
R/W R/W the function key function setting
LOC
0022h
40035
Key lock setting
R/W R/W the key lock setting
SLH
0024h
40037
High limit setting in SV limiter
R/W R/W the SV limiter upper limit setting
SLL
0026h
40039
Low limit setting in SV limiter
R/W R/W the SV limiter lower limit setting